VOLTAGE
Input Voltage and Limits
COMMAND NAME CMD CODE DESCRIPTION TYPE PAGED
DATA
FORMAT UNITS NVM
DEFAULT
VALUE
VIN_OV_FAULT_ LIMIT 0x55 Input supply overvoltage fault limit. R/W Word N L11 V Y 15.5
0xD3E0
VIN_UV_WARN_LIMIT 0x58 Input supply undervoltage warning limit. R/W Word N L11 V Y 6.3
0xCB26
VIN_ON 0x35 Input voltage at which the unit should start power
conversion.
R/W Word N L11 V Y 6.5
0xCB40
VIN_OFF 0x36 Input voltage at which the unit should stop power
conversion.
R/W Word N L11 V Y 6.0
0xCB00
VIN_OV_FAULT_LIMIT
The VIN_OV_FAULT_LIMIT command sets the value of the measured input voltage, in volts, that causes an input
overvoltage fault. The fault is detected with the A/D converter resulting in latency up to 100ms.
This command has two data bytes and is formatted in Linear_5s_11s format.
VIN_UV_WARN_LIMIT
The VIN_UV_WARN_LIMIT command sets the value of the input voltage that causes an input undervoltage warning.
The warning is detected with the A/D converter resulting in latency up to 100ms.
This command has two data bytes and is formatted in Linear_5s_11s format.
VIN_ON
The VIN_ON command sets the input voltage, in volts, at which the unit should start power conversion.
This command has two data bytes and is formatted in Linear_5s_11s format.
VIN_OFF
The VIN_OFF command sets the input voltage, in volts, at which the unit should stop power conversion.
This command has two data bytes and is formatted in Linear_5s_11s format.