DuraVent Type B Gas Vent - Specifications
Item Clearances
Maximum 
Height
Outer Tube Ø Materials
Locking 
Device
UL 
Listing 
ULC 
Listing 
Type B Vent 
Round 3"-8"
1 inch to combustibles 100 feet ⁄" larger than ID
Inner - .012" Aluminum
Outer - .018" Galvanized
DuraLock MH6357 CMH1276
Round 10" to 16"
See notes 2 & 5
1 inch to combustibles 100 feet 1" larger than ID
Inner - .016" Aluminum
Outer - .021" Galvanized
DuraLock MH6357 CMH1276
Round 18" to 30"
1 inch to combustibles 100 feet
2" larger than ID
See note 5
Inner - .020" Aluminum
Outer - .021" Galvanized
Screws MH6357 CMH1276
Oval Type B Vent 
4" and 5"
2" x 4" & 2" x 6" stud wall and 
1 inch to combustibles
See Note 3
2 ⁄" x 7 ⁄"
3 ⁄" x 10 ⁄"
Inner - .012" Aluminum
Outer - .018" Galvanized
Button Lock MH6357 CMH1276
Oval Type B Vent 
 6"
2" x 6" stud wall and 1 inch 
to combustibles
See Note 3 3 ⁄" x 12"
Inner - .012" Aluminum
Outer - .018" Galvanized
Button Lock MH6357 CMH1276
Type B Vent 3" to 6"
Round Liner
0"/Masonry 50 feet ⁄" larger than ID
Inner - .012" Aluminum
Outer - .018" Galvanized
DuraLock
MH14420
MH6357
CMH1407
DuraFlex AL Gas 
Relining 3" to 6"
0"/Masonry 50 feet ⁄" larger than ID .010" Aluminum Flex
Screws
DuraLock
MH14420 --
DuraConnect  
3" to 6"
1 inch to combustibles See Note 4 ⁄" larger than ID
.010" Aluminum Flex
.018" Galvalume
DuraLock MH14089 --
DuraConnect II  
3" to 6"
1 inch to combustibles See Note 4 ⁄" larger than ID
.010" Aluminum Flex
.018" Galvalume
DuraLock MH14089 --
NOTES
1.  Clearance to combustibles is 
the air space between vent and 
combustibles.
2. Maximum height varies with 
equipment over 50’, for taller 
applications refer to SDV sizing 
handbook  2. (L202). 14"-16" 
Require screws.
3. When oval is used on wall 
furnaces, minimum height required 
from bottom of furnce to cap is 12’, 
minimum 16” stud space.
4. Limited by sizing tables.
5. 18” pipe OD is one inch larger 
than ID and 20” - 30” OD is 2” 
greater than ID.