User Guide

3
Pascal 3.0 TCP Guide
lindab | we simplify construction
Lindab reserves the right to make changes without prior notice
2022-12-01
Bacnet TCP
In Bacnet TCP the status alarms are shown as Multi-state Input signals (object instance 62-179).
The alarms can have the following values: Normal(2); Blocked(3); Cancelled(4); Returned(6); Alarm(8).
Commands for these alarms are found in Analog Value-901 AlaCmdPtNo and Analog Value-902 AlaCmdExe. In Analog
Value-901 AlaCmdPtNo, set the alarm number of the Multi-state Input signal (62-179). Alarm numbers can also be seen
in Pascal Operate Alarm status.
In Analog Value-902 AlaCmdExe, the command for the selected alarm number is set. The possible commands are 1=Ac-
knowledge, 2=Block, 3=Unblock.
A Cancelled or Returned alarm will be set into Normal, after an Acknowledge command.
SRC commissioning parameters
For the 26 SRCs there are several commissioning parameters which both can be read and written to. However, as it is
commissioning parameters, all of them are not continuously updated in the Regula Master, so they must be read and writ-
ten, one SRC at a time. In the webserver Pascal Operate that is what is done for SRCs in Settings and Advanced menu
when clicking on the “Update settings” and “Confirm settings icons: