User Guide
LAMPING
NOTE: Socket manufacturers have suggested that socket may fail after 3 to 6
relampings. If this occurssocketcan be replacedby disconnectingmale
connectors(attachedto socketleads)from female connectors(attachedto
fixtureleads)and replacingit with a newsocketprocuredthroughLightolier
(Fig.
F).
A.
B.
c.
D.
Makesurethat poweris OFF
when Iamping or relamping. Remove
LAMP RING from socket cup by pulling straight down.
Inserl IAMP (MR16) between LAMP SPRINGS until face of lamp sits
firmly on GLASS LAMP GUARD (Fig, G),
Attach SOCKET to hi-pin prongs on LAMP,
Insert
IAMP RINGwith IAMP and GLASS lAMP GUARDbackinto
SOCKETCUP.
WARNING: LAMP MANUFACTURERS REQUIRE THE GLASS
LAMP GUARD BE IN PLACE BEFORE ENERGIZING LAMP,
AND THAT GREAT CARE MUST BE TAKEN THAT LAMP IS
FULLY COOLED BEFORE RELAMPING. AVOID FINGER
MARKS ON INSIDE OF LAMP FOR THEY MAY CAUSE
SHORT LAMP LIFE AND POSSIBLE BREAKAGE.
NOTE:1. LOWVOLTAGE FIXTURESshould be dimmed only with special
dimmers intended specifically for that purpose. UseLightolier Lytemode,
Scenist, Crescendo VA, Neptune VA, Precision VA, Easyset VA, Sunrise
VA, Radiant VA or equivalent products by others or variable autotransform-
ers or electronic dimmers intended for use with low voltage fixtures. 2.
Low voltage fixtures may produce audible sound when used with dimmers,
which may be objectionable in acoustically critical areas.
TRANSFORMER REPLACEMENT (Fig. H)
A.
B.
c.
D.
E.
F.
G.
H.
1,
J.
K.
L.
Make sure power is off.
Remove REFLECTOR TRIM from ceiling,
Pull CONVERSION KIT through the ceiling,
NOTE: For 1102P1, loosen LOCKING SCREW (Fig. C)
Detach frame-in kit SOCKET CUP and unscrew MALE ADAPTER
from CONVERSION KIT,
Unscrew CONVERSION KIT SCREWS and pull U-BRACKETS apart,
Unscrew TRANSFORMER SCREWS and remove TRANSFORMER,
Unsplice MALE ADAPTER from TRANSFORMER,
Cut secondary (red) leads 6“ to 8“ from transformer and discard
faulty transformer.
Re-assemble new transformer to U-BRACKET splice secondary
(red) leads to socket leads. Tie a knot with these leads to avoid
strain on splices,
Re-splice male adapter leads to primary leads of the TRANSFORMER
Tie a knot with these leads to avoid strain on splices,
Reassemble “U-brackets” and secure with “conversion kit screws.”
Re-install CONVERSION KIT bv following instruction of section 2
through 5 of this INSTRUCTION. -
WARNING: USE ONLY WITH FRAME-IN KITS
PROVIDED BY LIGHTOLIER INC. USE
OF OTHER
MANUFACTURER’S FRAME-IN KITS VOIDS THE UNDER-
WRITERS LABORATORIES LISTING AND COULD Consti-
tute A FIRE HAZARD.
IS:1920LV
0892
Page 2 of 2
MALE CONNECTORS
INSULATING
(Attached to Socket Wires)
SLEEVING
z“
FEMALE CONNECTORS
y
(Attached to Fixture Wires)
MR16 SOCKET
1
FIG. F
R
.
SOCKET
LAMP -
LAMP SPRING
&
!
L
~,MARyLE~s‘U-BRACKETS
TRANSFORMER MOUNTING SCREW (2)
I
FIG. H