DETERMINE AND SET WIRING TYPE
Read the descriptions of the different wiring types to determine which setting will be correct for each application. Once the wiring type 
is determined, set the selector dial accordingly.
OPTN
PROG
DIAG
FSTS
TS
T
E2
D1
C2
B2
SELECTOR DIAL
IMPORTANT NOTES:
1. External interlocks may be used with all functional modes.
2. Auxiliary devices are any devices that have only dry contacts. 
Examples: photocell, loop detector, pneumatic or electrical 
treadles, radio controls, one button stations, pull cords, etc.
3. Open override means that the door may be reversed while 
closing by activating an opening device without the need to use 
the stop button first.
4. When the door is in a stopped position other than fully closed, 
and a safety input is activated (LMEP or EDGE), the Restricted 
Close (RC) feature will allow a close command when the close 
button is pressed and held. The operator will begin closing after 
5 seconds. If the close button is released the door will stop.
  When in E2 mode, the door will move to the fully open position.
LIFTMASTER MONITORED ENTRAPMENT PROTECTION (LMEP) 
DEVICE IS REQUIRED
A LiftMaster Entrapment Protection (LMEP) device is required for 
the following wiring types.
LIFTMASTER MONITORED ENTRAPMENT PROTECTION (LMEP) 
DEVICE IS RECOMMENDED
A LiftMaster Entrapment Protection (LMEP) device is 
recommended for the following wiring types.
B2    Momentary contact to open, close and stop, plus wiring for 
sensing device to reverse and auxiliary devices to open and 
close with open override. Programmable mid stop available 
with this wiring type. Compatible with 3-Button Station, 
1-Button Station, 1 and 3-Button Remote Control.
TS (TIMER SECURE)
   This mode will attempt to close the door from any position 
except when fully closed, or when a safety input is present. 
The stop button will not disable the Timer-To-Close at any 
position. To disable the Timer-To-Close in this mode, 
installation of a defeat switch is required (see wiring 
diagram).
  Momentary contact to open, close, and stop with open 
override and Timer-To-Close. Every device that causes door 
to open, including a reversing device, activates the Timer-
To-Close. Auxiliary controls can be connected to open input 
to activate the Timer-To-Close. If the timer has been 
activated, the open button and radio control can recycle the 
timer. The Timer-To-Close will function from the 
programmable mid stop with this wiring type. Compatible 
with 3-Button Station, 1-Button Station and 1 and 3-Button 
Remote Control.
NOTE: A Programmable “Car Dealer Mode” available.
T   Momentary contact to open, close, and stop, with open 
override and Timer-To-Close. Every device that causes the 
door to open, except any safety edge input device, activates 
the Timer-To-Close. Auxiliary controls can be connected to 
open input to activate the Timer-To-Close. If the Timer-To-
Close has been activated, the open button and radio control 
can recycle the timer. The stop button will deactivate the 
timer until the next command input. The Timer-To-Close will 
function from the programmable mid stop with this wiring 
type. Compatible with 3-Button Station,1-Button Station 
and 1 and 3-Button Remote Control. 
NOTE: Programmable “Car Dealer Mode” available.
FSTS  Momentary button contact for open, close and stop 
programming. User set mid stop. User set Timer-To-Close. 
The single button station opens the door to the full open 
limit bypassing the mid stop and activates the Timer-To-
Close, putting the operator in TS mode until the door 
reaches the down limit, or is stopped in travel. At which 
time the operator enters the B2 mode. 
   Compatible with 3-Button Station, 1-Button Station, 1 and 
3-Button Remote Control. A 1-Button remote control in 
FSTS mode will open only with the Timer-To-Close, 
bypassing a programmed mid stop. The Timer-To-Close will
reset and reverse when closing.
C2   Momentary contact to open and stop with constant pressure 
to close, open override plus wiring for sensing device to 
reverse. Programmable mid stop available with this wiring 
type. Compatible with 3-Button Station and 1-Button 
Station.
E2   Momentary contact to open with override and constant 
pressure to close. Release of close button will cause door to 
reverse (roll-back feature) plus wiring for sensing device to 
reverse. Compatible with 3-Button Station.
D1   Constant pressure to open and close with wiring for sensing 
device to stop. Compatible with 2 or 3-Button Station.
BASIC PROGRAMMING
3