TABLE OF CONTENTS INTRODUCTION WARNING General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 Agency Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INTRODUCTION AGENCY REQUIREMENTS WARNING Installation and testing to factory specifications shall be performed by factory authorized personnel for proper operation in accordance with the latest National Fire Protection Association (NFPA), Underwriters Laboratories (UL), National Electrical Code (NEC), local, state, county, district and/or other applicable building and fire standards, guidelines, regulations and codes including, but not limited to, all appendices and amendments and the requirements of the
I N S TA L L AT I O N NING WARNING IMPORTANT INSTALLATION INSTRUCTIONS ON WARNING To reduce the risk of SEVERE INJURY or DEATH: 1. READ AND FOLLOW ALL INSTALLATION WARNINGS AND INSTRUCTIONS. 2. NEVER connect release device to power source until instructed to do so. 3. DO NOT use this device without fusible links installed. SEMENT TION 4. Concrete anchors MUST be used if mounting release device into masonry. 5. DO NOT exceed maximum pull rating of 40 lbs. on releasing device.
ING WWARNING IRING ON WARNING To reduce the risk of SEVERE INJURY or DEATH: • ALL electrical connections MUST be made by a qualified individual. • Disconnect power at the fuse box BEFORE proceeding. Release device MUST be properly grounded and connected in accordance with local electrical codes. • Installation of ALL wiring and connections, including Class 1 and Class 2 circuits, shall be performed in accordance with, but not limited to, the latest NFPA, UL and N.E.C. standards and codes.
WIRING WIRE ROUTING Mechanical Reset Plunger High Voltage Wiring Ground L2 L1 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Low Voltage Wiring Power Strip Annunciator Wiring with Sleeve Voice Board Wiring PARTS KIT LMEOLRES-10 Wire Jumper 10k Ohm Resistor Refer to wiring section for proper application of these parts.
WIRING WIRING DIAGRAM Replace batteries every 2 years. Field wiring shall consist of 22-18 AWG wiring. Use only 250Vac, 3 Amp, 3 AG, Slo-Blo fuses. 1. Supervised, power limited circuit, 20 Ohm maximum line impedance. 2. Unsupervised power limited circuit, 20 Ohm maximum line impedance. 3. Maximum of 4 Class B Style A detectors. 4. Maximum of 2 Class B Style W notification appliances. 0.5 Amp at 24 Vdc maximum. Supervised non-power limited circuit.
WIRING CONNECTIONS OF INITIATING DEVICES AND ACCESSORIES WARNING A maximum of 4 smoke detectors may be installed with this device. Refer to NFPA 72 and NFPA 80 for instructions concerning proper placement and detection coverage. End-of-line devices must be installed for supervision of electrical power to 4-wire smoke detector. When using 4-wire smoke detectors with this device, electrical supervision must be provided by means of a UL/ULC listed end-of-line relay.
WARNING WIRING CONNECTIONS OF INITIATING DEVICES AND ACCESSORIES (cont’d) CAUTION To prevent DAMAGE to the circuit board, ALL connections from terminals 3 through 16 MUST be dry contact type. Relay Module Installation In lieu of smoke detectors, the release device may be put into alarm by the fire alarm control panel. Most commonly, a relay module is used as an interface between the fire alarm control panel and the release device.
WIRING OPTIONAL CONNECTIONS (cont’d) VOICE BOARD OPTION The voice board provides one of two verbal warnings that the fire door is closing. Typically, depending on the length of the delay chosen on the release device, a warning tone will occur prior to the message, which is approximately 10 seconds in length (for example, a 20 second delay setting on the release device will result in a 10 second warning tone followed by the verbal warning message).
TESTING TEST PROCEDURES WARNING TO BE PERFORMED BY FACTORY AUTHORIZED PERSONNEL ONLY! CLEAR FIRE DOOR OPENING AND PROHIBIT TRAFFIC THROUGH DOOR OPENING WHILE TESTING! Testing does not affect normal operation of alarm system when connected to release device/control panel.
TROUBLESHOOTING OPERATIONAL CHECKLIST WARNING POWER Is the red LED, labeled “Power,” located on the bottom of the enclosure lit? To prevent possible SERIOUS INJURY or DEATH: • Clear fire door opening and prohibit ALL traffic through door opening while trouble shooting. CAUTION Is the Red LED Lit? Yes Move on. No Check power connections per Wiring Diagram.
WARNING WARNING MAINTENANCE MAINTENANCE REQUIREMENTS CAUTION WARNING The release device has no scheduled maintenance requirements. The unit has been designed and tested for use in dry, indoor locations. Testing of the unit at least once every 90 days is recommended, but test intervals shall ultimately be subject to criteria established by the Authority Having Jurisdiction (AHJ). To avoid SERIOUS PERSONAL INJURY or DEATH: • Stand clear of path of door.
ACCESSORIES AND REPLACEMENT PARTS ACCESSORIES ITEM 1 2 3 4 5 PART # LM8100 LM8100T LM8100I LM2WB LM2WTB 6 7 LM4WB LM4WTB 8 9 10 11 LM1424 LM1412 LMTH135 LMTH194 DESCRIPTION Smoke Detector - 120V Photo Smoke Detector - 120V Photo with Thermal Smoke Detector - 120V Ion Smoke Detector - 12/24Vdc 2-Wire Photo Smoke Detector - 12/24Vdc 2-Wire Photo with Thermal Smoke Detector - 12/24Vdc 4-Wire Photo Smoke Detector - 12/24Vdc 4-Wire Photo with Thermal and Form C Relay Smoke Detector - 24Vdc Ion Smoke Detect
APPENDIX ACCESSORY COMPATIBILITY GUIDE SMOKE DETECTORS MODEL NO. DESCRIPTION SYSTEM SENSOR MODEL NO. LM2WB 24Vdc 2-Wire Photo 2W-B LM2WTB 24Vdc 2-Wire Photo with Thermal 2WT-B LM4WB 24Vdc 4-Wire Photo 4W-B LM4WTB 24Vdc 4-Wire Photo with Thermal & Form C Relay 4WT-B LM1424 24Vdc Ion #1424 HEAT DETECTORS MODEL NO. DESCRIPTION SYSTEM SENSOR MODEL NO. CHEMTRONICS MODEL NO. EDWARDS SYSTEM TECHNOLOGY (EST) MODEL NO.