User Guide
Limit Switch
Enclosure
Explosion Proof
Motor
Junction Box
(As Required)
Control
Station
Electrical
Enclosure
SEE
NOTE 7
Coil Cord or
Take-Up Reel
(Optional)
Safety Switch (Optional)
1
3
2
1
4
5
5
HAZARDOUS LOCATION
CLASS I, II, DIVISION 1
GROUP D, E, F & G
NON -
HAZARDOUS
LOCATION
1
2
3
4
5
6.
7.
8.
9.
NON-ENERGY STORING DEVICES SUCH AS LIMIT
SWITCH ASSEMBLY, SAFETY SWITCH, AND
OPERATOR CONTROL STATION.
FACTORY INSTALLED JUNCTION BOX WITH
INTRINSICALLY SAFE WIRING FOR CONNECTION
TO CONTROL AND LIMIT SWITCHES AS
CLASS I, DIV. 1, GROUP D
CLASS II, DIV. 1, GROUPS E F & G.
EXPLOSION PROOF MAKE-UP BOX FACTORY
INSTALLED.
CONDUIT SEAL FACTORY INSTALLED.
CONDUIT SEAL REQUIRED.
INSTALLATION MUST BE IN ACCORDANCE WITH
ARTICLE 500 OF THE NATIONAL ELECTRICAL CODE.
THE NON-HAZARDOUS LOCATION OR CONTROL
ROOM MOUNTED EQUIPMENT SHOULD NOT USE
OR GENERATE MORE THAN 250Vrms.
NO CHANGES SHALL BE MADE TO THIS DOCUMENT
WITHOUT THE NOTIFICATION AND APPROVAL OF
FACTORY MUTUAL.
MODEL GJX, 1/2 & 1 HP
MODEL GTX, 1/2 & 1 HP
MODEL GJX, 2 HP
CLASS I, DIVISION 1, GROUP D
CLASS II, DIVISION 1, GROUPS E, F & G
CLASS I, DIVISION 1, GROUP D
CLASS II, DIVISION 1, GROUPS E & F
SUITABLE FOR
1
5