Submittal Sheet
RNC4-TPF Performance
(HVI certified)
Net supply airflow in cfm against external static pressure
Sensible Efficiency: Thermal
Effectiveness: Based on temperature differential between
the two airstreams
Efficiency: Takes into account all power inputs
RNC4-TPF
HEAT RECOVERY VENTILATOR
ENGINEERING DATA
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two airstreams. It is easily removed for
cleaning or service.
MOTORS AND BLOWERS
Each airstream has an independent motorized impeller with multiple fan speed operations
FILTERS
Washable air filters in exhaust and supply airstreams.
MOUNTING THE HRV
“S” hooks and hanging straps supplied with the unit.
DEFROST
Temperature sensor activated, periodically shuts down supply motor.
CASE
20 gauge prepainted galvanized steel for superior corrosion resistance, insulated to prevent exterior
condensation. Drain connections Two 1/2 in (12 mm) OD.
Balancing ports are located on unit.
INSTALLER SELECTABLE HIGH SPEED SETTINGS
Adjustable DIP switches are located on the circuit board, Hi3 is the factory setting.
Refer to the Installation manual or the adjustment instructions.
ELECTRONICS
The optional controls can be wall mounted in a central location of the home. 3 wire 20 gauge (min.) 100
ft length (max.).
CONTROL OPTIONS
ACCESSORY OPTIONS
99-163 Duct Heater w/Electronic SCR Thermostat - 1 kW, 6 in (152 mm)
99-184 Weatherhoods - Two 4 in (102 mm)
99-194 4" Dual Hood - One 6 in (152 mm) opening for supply and exhaust.
99-080-04 Wall Mount Bracket
DIMENSIONS RNC4-TPF WEIGHT 35 lbs (16 kg) SHIPPING WEIGHT 38 lbs (17 kg)
Units carry a lifetimewarranty on the
HRV core and a 5 year replacement
parts warranty.
_
_
_
_
_
_
_
_
_
Date:
Tag: Qty:
Project:
Engineer:
Contractor:
Supplier:
Quote #:
Submi ed By:
All units conform to CSA and UL
standards
Front View
Top View
Square Core - Fan Defrost
@ 0.2 in (50 Pa)
88 cfm (42 L/s)
82 cfm (39 L/s)
75 cfm (35 L/s)
68 cfm (32 L/s)
@ 0.3 in (75 Pa)
@ 0.4 in (100 Pa)
@ 0.5 in (125 Pa)
External Static Press re
Airflow
Max. Temperature Recovery
78%
Sensible EffecĀtiveness
@ 55 cfm (26 L/s)
32°F (0°C )
75%
Sensible Efficiency
@ 55 cfm (26 L/s)
32°F (
0°C )
67%
Sensible Efficiency
@ 60 cfm (28 L/s)
-13°F (-25°C )
61%
VAC @ 60Hz 120
Amp raĀting
0.48
Fresh Air
From Outside
Stale Air To
Outside
Fresh Air To
Inside
Stale Air
From Inside
NOTE: All specifications are subject
to change without notice.
18 3/4" (476 mm)
17 7/8" (454 mm)
19 1/4" (489 mm)
@ 0.1 in (25 Pa)
95 cfm (45 L/s)
59 cfm (28 L/s)
50 cfm (24 L/s)
@ 0.6 in (150 Pa)
@ 0.7 in (175 Pa)
Watts - High Speed 57
Watts - Low Speed
38
HI 3
HI 2
HI 1
LOW
Note: Front clearance
of 25 in (635 mm) is
recommended for
servicing unit. All ducts
use 4 in (102 mm)
round collars,
balancing dampers are
located in all air
streams.
TIMER OPTIONS
99-DET01 Lifebreath 20/40/60 Minute Timer - Initiates High speed Ventilation for 20, 40 or 60 minutes.
99-BC03 Lifebreath Ventilation Control
•
•
•
Continuous Low fan speed
Humidity control through adjustable
Dehumidistat
3 modes of operation: Ventilation,
Recirculation, 20/40
• Compatible with 99-DET02 Wireless Timers
• 3 wire connection
99-DXPL02 Lifebreath Digital Control
• 5 speed operation on each mode
• Humidity control through adjustable
Dehumidistat
• 5 user selectable operational modes: Continuous
Ventilation, Continuous Recirculation, 20 ON/40
OFF, 10 ON/50 OFF, 20 ON/40 Recirculation
• 20/40/60 min. High speed override button
• Compatible with 99-DET02 Wireless Timers
• 3 wire connection
99-BC02 Lifebreath Ventilation Control
• 2 speed fan setting (Low/High)
• Humidity control through adjustable
Dehumidistat
• Compatible with 99-DET02 Wireless Timers
• 3 wire connection
between timer and main wall control if timer is out of range.
99- BC04 Lifebreath Ventilation Control
• 2 speed fan setting (Low/High)
• 2 modes of operation: Ventilation, 20/40
• Compatible with 99-DET02 Wireless
Timers
• 3 wire connection
99-DH01 Lifebreath Dehumidistat
• Humidity control through adjustable
Dehumidistat
• 3 wire connection
3 wire connecon.
99-DET02 Lifebreath WIRELESS 20/40/60 Minute Timer - Initiates High speed Ventilation for 20, 40 or 60
minutes. Wirelessly connects to main control for ease of install ation. 40' approximate range.
99-RX02 Lifebreath WIRELESS Repeater - Used to extend range of 99-DET02 Wireless Timers. Plugs into
120V power outlet. Wirelessly connects to main control and 99-DET02. Install at halfway point