UPStation GXT™ 6 & 10 kVA 208V & 240V USER MANUAL English
IMPORTANT SAFETY INSTRUCTIONS WARNING: Opening or removing the cover may expose you to lethal voltages within this unit even when it is apparently not operating and the input wiring is disconnected from the electrical source. Observe all cautions and warnings in this manual. Failure to do so MAY result in serious injury or death. Refer all UPS and battery service to qualified service personnel. Do not attempt to service this product yourself. Never work alone. 1. SAVE THESE INSTRUCTIONS.
8. Never block or insert any object into the ventilation holes or other openings. 9. DO NOT CONNECT equipment that could overload the UPS or demand DC current from the UPS, for example: electric drills, vacuum cleaners, laser printers, hairdryers or any appliance using half wave rectification. 10. Storing magnetic media on top of the UPS may result in data loss or corruption. 11. Turn the UPS off and isolate the UPS before cleaning. Use only a soft cloth, never liquid or aerosol cleaners.
INTRODUCTION Congratulations on your choice of the UPStation GXT™ Uninterruptible Power System (UPS). It provides conditioned power to microcomputers and other sensitive electronic equipment. Upon generation, AC power is clean and stable. However, during transmission and distribution it may be subject to voltage sags, spikes, or complete power failure, which may interrupt computer operations, cause data loss, or even damage equipment. The UPStation GXT protects equipment from these disturbances.
MAJOR COMPONENTS Rectifier/PFC INPUT Output Transformer GXT 208X, 230X, & 240X models only Inverter EMI/RFI Filter EMI/RFI Filter OUTPUT Static Bypass Battery Battery Charger EMI /RFI FILTERS These UPS components provide surge protection, and filter both electromagnetic interference (EMI) and radio frequency interference (RFI). They minimize any surges or interference present in the utility line and keep the sensitive equipment protected.
STATIC BYPASS The UPStation GXT provides an alternate path for utility power to the connected load, in the unlikely event of a UPS malfunction. Should the UPS have an overload, over temperature, or UPS failure condition, the UPS automatically transfers the connected load to BYPASS providing the bypass voltage is within specification. BYPASS operation is indicated by an alarm and an illuminated BYPASS LED (other LED’s may be illuminated to indicate any diagnosed problem).
INSTALLATION These instructions are for use by competent personnel only. INSTALLATION CONSIDERATIONS Detailed instructions to help you install the UPS are provided in the following pages; however, you should give some consideration to the proposed environment in which the UPS is to be installed, and carry out some preparatory work. UNPACKING AND INSPECTION Follow unloading instructions printed on the carton.
Model # GXT6000T GXT10000T AIRFLOW Cfm 130 270 m 3h 221 459 DISSIPATION* Watts 504 840 K Btu/hr 1.7 2.8 OUTPUT RATING** VA 6000 10000 Watts 4200 7000 * Increase dissipation 25% for 208X, and 240X transformer models. ** Decrease output rating 10% for 208 and 208X model. ELECTRICAL INSTALLATION CONSIDERATIONS This UPS must be installed by competent electrical personnel and wired in accordance with local/national electrical codes. The following information is provided for your guidance.
Connecting the UPS Power cables Power cables connect to screw terminals on a terminal block that is located behind the rear mounted cable box (see figure). Permanent wiring must be routed to the cable box using appropriate materials as required by local codes. Connection of optional remote battery cabinets Full installation instructions are provided with these cabinets. Safety/EMC certification limits the use of these terminals to Liebert supplied options.
GXT6000T / 10000T - 208 UPS ONLY Models whose part number ends with a “208” are NOT fitted with an isolating output transformer and are NOT separately derived sources under the NEC. The output L1 terminal is connected to the input L1 terminal and must not be connected to ground at the UPS (see NEC 250-5d, 250-26, 250.91, 250.92).
NOTES FOR GXT6000T / 10000T - 208 UPS ONLY 1. The installer must provide circuit breaker protection according to local codes. The UTILITY disconnect must be within sight of the UPS. Maintain service space around the UPS or use flexible conduit. 2. The installer must provide output distribution panels and circuit breaker protection according to local codes. Output circuits must not share a common conduit with input circuits or any other wiring. 3.
GXT6000T / 10000T - 208X UPS ONLY Models whose part number ends with a “208X” are fitted with a single-phase isolating output transformer and are separately derived sources. The output neutral is already bonded to ground on the output terminals with a Bonding Jumper (see NEC 250-5d, 250-26, 250.91, 250.92). The output L1 and L2 terminals are not connected to the input L1 and L2.
NOTES FOR GXT6000T / 10000T - 208X UPS ONLY 1. The installer must provide circuit breaker protection according to local codes. The utility disconnect must be within sight of the UPS. Maintain service space around the UPS or use flexible conduit. 2. The installer must provide output distribution panels, circuit breaker protection, or emergency disconnect switches according to local codes. Output circuits must not share a common conduit with input circuits or any other wiring.
GXT6000T / 10000T - 240X ONLY Models whose part number ends with a “240X” are fitted with a single-phase isolating output transformer and are separately derived sources. The output neutral is already bonded to ground on the output terminals with a Bonding Jumper (see NEC 250-5d, 250-26, 250.91, 250.92). The output L1 and L2 terminals are not connected to the input L1 and L2.
NOTES FOR GXT6000T / 10000T - 240X ONLY 1. The installer must provide circuit breaker protection according to local codes. Maintain service space around the UPS or use flexible conduit. 2. The installer must provide output distribution panels, circuit breaker protection, or emergency disconnect switches according to local codes. Output circuits must not share a common conduit with input circuits or any other wiring. IMPORTANT - Distribute any 120VAC loads evenly between L1 AND L2. 3.
STABILIZERS / LEVELING FEET When the UPS is located in its final position before or after wiring, it is necessary to fit stabilizer brackets and, if necessary, adjust the leveling feet. If the UPS is wired using a rigid wiring system, then movement of the UPS must be prevented by winding down the 4 leveling feet under the UPS as shown below. For UPS wired with flexible cables, this is optional. Note - Access to the leveling feet is obstructed by the stabilizer brackets, on the GXT10000 models.
FERRITE BEAD INSTALLATION When using either of the options below, to reduce the risk of radio interference, fit the ferrite assemblies supplied with the UPS as follows: Serial Communications Attach the smaller enclosed ferrite bead clamp to the communication cable as shown in the drawing using the following directions: • • • • Open the ferrite bead. Place the communication cable inside the ferrite bead groove.
COMMISSIONING THE UPS Output Voltage Selector Switches The Output Voltage Selector Switches, located on the rear of the UPS, are designed to allow selecting or changing the desired output voltage to match the utility. The settings to choose from are 208, 220, 230 and 240 VAC output.
CONTROLS AND INDICATORS Fault Indicator UPS ON / Alarm Silence / Manual Battery Test BYPASS UPS ON BATTERY Output OFF / Bypass AC INPUT Load / Battery Level Indicators Fault Indicator (Red) The Fault indicator is illuminated if the UPS has detected a problem. Also, one or more of the load/battery level indicators may be illuminated (refer to Troubleshooting Guide). BYPASS Indicator (Amber) The BYPASS indicator is illuminated when the UPS is operating from BYPASS power.
Load/Battery Level Indicators (4 Green, 1 Amber) The Load/Battery Level indicators have dual functions. During NORMAL mode operation LED indicators display the approximate electrical load placed upon the UPS; and during battery mode operation LED indicators display approximate battery capacity. The UPStation GXT is equipped with automatic and remote battery test features.
TM Intellislot Communications Port DB-9 Communications Port GXT 6 & 10 kVA Component Diagram 208 Models Shown DB-9 Communicaions Port Output Voltage Selector Switches TM Intellislot Communications Port Output Voltage Selector Switches Breakers Battery Breaker Input Breaker Battery Breaker Input Output Output Breaker Hardwire Terminal Blocks Hardwire Terminal Blocks Adjustable leveling feet 21
OPERATING MODES NORMAL MODE OPERATION- UPS mode During normal operation, utility power provides energy to the UPS. The filters, the power factor correction circuit and the inverter process this power to provide computer grade power to connected loads. The UPS maintains the batteries in a fully charged state. The four green Leads indicate an approximate level of load in 25% increments. If the UPS becomes loaded beyond full rating, the fifth (amber) LED indicator will illuminate and sound an alarm.
BYPASS MODE OPERATION During BYPASS operation, utility power provides energy to your load and maintains the batteries in a fully charged state. The BYPASS will automatically power the load temporarily during overloads of the inverter, when diagnostics detect equipment problems, or when the operator selects BYPASS operation. The four green LEDs indicate an approximate level of load in 25% increments.
MANUAL OPERATION WITH UTILITY AVAILABLE Under normal circumstances, the UPS will be operated with utility available. The UPS can operate in three possible modes with utility available: NORMAL MODE OPERATION - UPS ON LED will be on and the inverter will provide power to the load. BYPASS MODE OPERATION - BYPASS LED will be on and the bypass will provide power to the load directly from the utility. OUTPUT OFF MODE OPERATION - UPS ON and BYPASS LEDs will be off and the load will not have power.
POWERING DOWN THE UPS WITH UTILITY AVAILABLE 1. Shutdown all connected load equipment. 2. Press the OUTPUT OFF/BYPASS button once until a "beep" is heard. The UPS ON LED will extinguish and the BYPASS LED will light if the BYPASS voltage is within an acceptable range. The load is now powered through the BYPASS and there is no UPS protection. The UPS will remain in BYPASS MODE OPERATION until the user continues with the next step to turn the UPS off. 3.
POWERING UP THE UPS WITHOUT UTILITY 1. Ensure the load equipment is turned off, and all loads are properly connected to the UPS output. 2. Verify that the BATTERY, INPUT, AND OUTPUT circuit breakers remain closed. 3. Press the UPS ON/ALARM/BATTERY TEST button for at least one second until you hear the audible alarm emit a “double beep" to signal acceptance of the command. After a short delay, the BATTERY LED should light.
COMMUNICATIONS UPS MONITORING The UPStation GXT UPS has the capability of being monitored with stand alone computers, network workstations, network servers, or UNIX hosts via the DB-9 socket located on the rear of the UPS. This capability is used in applications requiring the UPS to provide status and power monitoring information to the computer system.
COMMUNICATIONS INTERFACE PORT The UPStation GXT UPS contains a standard DB-9 socket located on the rear of the UPS unit.
TROUBLESHOOTING The information below indicates various symptoms a user may encounter in the event the UPStation GXT develops a problem. Use this information to determine whether external factors cause the problem and how to remedy the situation. 1. The fault indicator will illuminate indicating the UPS detected a problem. 2. An alarm will sound, alerting that the UPS requires attention. 3.
AUDIBLE ALARM CONDITIONS CONDITION ALARM Battery mode (utility failure) One short beep every ten seconds Low battery Two short beeps every five seconds Output overload (bypass) One short beep every half second Over temperature (bypass) One second beep every four seconds DC Bus over voltage (bypass) One second beep every four seconds PFC failure (bypass) One second beep every four seconds Inverter failure One second beep every four seconds Battery Test failure Two second beep every minute T
TROUBLESHOOTING GUIDE PROBLEM CAUSE Fault indicators and all load level LED's are illuminated UPS overloaded or load equipment is faulty Fault indicators and diagnostic LED A are illuminated UPS internal fan has a problem or UPS shutdown due to temperature condition. Load is on bypass power.
MAINTENANCE The UPStation GXT UPS requires very little maintenance. The batteries are valve regulated, nonspillable, lead acid, and should be kept charged to obtain their designed life. The UPS continuously charges the batteries when connected to the Utility supply. When storing the UPS for any length of time, it is recommended to apply power to the UPS for at least 24 hours every four to six months to ensure full recharge of the batteries.
SPECIFICATIONS MODEL NUMBER MODEL RATING VA/W (max) GXT6000T-208 GXT10000T-208 5400 / 3780 9000 / 6300 DIMENSIONS: mm (in) Unit W xDxH 260 x 555 x 803 340 x 650 x 960 (10.3 x 21.9 x 31.6) 400 x 850 x 1065 (13.4 x 25.6 x 37.8) 510 x 840 x 1235 (15.8 x 33.5 x 41.9) (20.1 x 33.1 x 48.
SPECIFICATIONS MODEL NUMBER MODEL RATING VA/W (max) GXT6000T-208X GXT10000T-208X 5400 / 3780 9000 / 6300 DIMENSIONS: mm (in) Unit W xDxH 260 x 555 x 803 340 x 650 x 960 (10.3 x 21.9 x 31.6) 400 x 850 x 1065 (13.4 x 25.6 x 37.8) 510 x 840 x 1235 (15.8 x 33.5 x 41.9) (20.1 x 33.1 x 48.
SPECIFICATIONS MODEL NUMBER MODEL RATING VA/W (max) GXT6000T-240X GXT10000T-240X 6000 / 4200 10000 / 7000 DIMENSIONS: mm (in) Unit W xDxH 260 x 555 x 803 340 x 650 x 960 (10.3 x 21.9 x 31.6) 400 x 850 x 1065 (13.4 x 25.6 x 37.8) 510 x 840 x 1235 (15.8 x 33.5 x 41.9) (20.1 x 33.1 x 48.
LIMITED WARRANTY Liebert Corporation extends the following LIMITED WARRANTY to the purchaser and to its customer (collectively referred to as the "Purchaser"): the enclosed Uninterruptible Power System (UPS) and components are free from defects in materials and workmanship under normal use, service, and maintenance FOR A PERIOD OF TWO YEARS FROM THE DATE OF ORIGINAL PURCHASE from Liebert or the Liebert dealer or retailer.
UPStation GXT™ 6 & 10 kVA 208V & 240V Technical Support Global Services Applications U.S.A. Outside the U.S.A. U.K. France Germany Italy Netherlands E-mail Web site Worldwide FAX tech support 1-800-LIEBERT 1-800-222-5877 614-841-6755 +44 (0) 1793 553355 +33 (0) 1 43 60 01 77 +49 89 99 19 220 +39 2 98250 1 +31 (0) 475 503333 upstech@liebert.com http://www.liebert.