POWER AVAILABILITY POWERSURE™ PSP USER MANUAL 350-650 VA 120V
TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . 1 INTRODUCTION & SYSTEM DESCRIPTION . . . . . . . . . . . . . . . . . 4 Front View of UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Rear View of UPS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 MAJOR COMPONENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Transient Voltage Surge Suppression (TVSS) & EMI / RFI Filters . . . . . . . . . . .
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Cleaning the UPS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Maintaining Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Battery Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Battery Replacement Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . 19 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important safety instructions that should be followed during the installation and maintenance of the Uninterruptible Power System (UPS) and its batteries. Please read this manual thoroughly before attempting to install or operate this UPS. Read all safety, installation, and operating instructions before operating the UPS. Adhere to all warnings on the unit and in this manual. Follow all operating and user instructions.
! WARNING If your UPS demonstrates any of the following conditions, turn off and unplug your UPS from the outlet and contact your local dealer, Liebert representative or Liebert Worldwide Support Group: • The power cord or plug is damaged. • Liquid has been spilled on the UPS. • The circuit protector trips frequently. • The UPS does not operate in accordance with the user manual. CONDITIONS OF USE: The input receptacle must be within 6 feet (1.8 meters) of the UPS.
! CAUTION BATTERY HANDLING PRECAUTIONS Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and required precautions. Keep unauthorized personnel away from the batteries. A battery can present a risk of electrical shock and high short-circuit current. The following precautions should be observed when working on batteries: • Remove watches, rings, and other metal objects. • Use tools with insulated handles. • Do not dispose battery or batteries in a fire.
INTRODUCTION & SYSTEM DESCRIPTION Congratulations on your choice of the Liebert PowerSure™ PSP Uninterruptible Power System (UPS). It provides filtered AC power to sensitive electronic equipment and other critical loads. The PowerSure PSP is an off-line UPS designed for desktop applications. It provides perfect one-to-one power protection for electronic equipment such as PCs, point-of-sale displays, home office equipment and similar electronic gear.
Front View of UPS Power ON/OFF/ Alarm Silence* Utility Indicator* (Green) Battery Indicator* (Green/Amber) Fault Indicator* (Red/Green) * For details, see Controls and Indicators section 5
Rear View of UPS USB port*** DIP switches** DB-9 port*** Site Wiring Fault Indicator (Red)** Data Line Protection Connectors (2)*** Phone/Fax/DSL/ Internet/Modem devices Orange output receptacles (4)* Battery backup + surge protection Black output receptacles (2)* Surge protection only Input circuit protector 6-ft. (1.
MAJOR COMPONENTS Input L TVSS & EMI / RFI Filters Transfer Switch Battery Charger Battery Output L Inverter N N G G Transient Voltage Surge Suppression (TVSS) & EMI / RFI Filters These UPS components provide surge protection and filter electromagnetic interference (EMI) and radio frequency interference (RFI). They minimize surges or interference present in the utility line and keep the sensitive equipment protected.
WHAT’S INCLUDED The PowerSure PSP is shipped with the following components: • Quick-Start guide • PowerSure family user manual on CD • Warranty card • MultiLink™ software CD • MultiLink serial cable (M3LS9P9S), 10 ft. (3m) • RJ-11 cord, 7 ft. (2.1 m) • USB cable, 6 ft. (1.8m) PowerSure PSP MultiLink software CD USB cable 6 ft. (1.8m) RJ-11 cord 7 ft. (2.1m) 8 MultiLink serial cable (M3LS9P9S) 10 ft.
INSTALLATION 1. Visually inspect the UPS for freight damage. Report damage to the carrier and your local dealer, Liebert representative or the Liebert Worldwide Support Group. 2. Decide where to place the PowerSure PSP. Install the UPS indoors in a controlled environment, where it cannot be accidentally turned off. Place it in an area of unrestricted airflow around the unit, away from water, flammable liquids, gases, corrosives, and conductive contaminants.
5. Connect Phone/Fax/DSL/Internet/Modem devices to data line connectors. Serial port for MultiLink cable connection 6. Press and release the ON/OFF/Alarm Silence button to turn on the UPS. The UPS will beep and the Utility Indicator will illuminate (green). 7. Turn on connected equipment. 8. Communication options (see Communications section for details): Option 1—Serial Communications Serial communications provides parametric data, for example, input voltage and battery voltage. a.
CONTROLS AND INDICATORS ON/OFF/Alarm Silence Button This button controls output power to the connected load and has three functions: • ON • OFF • Alarm Silence ON/OFF/Alarm Silence ON When the UPS is off, pressing and releasing the main ON/ OFF button will start the UPS, and an audible alarm sounds briefly. The UPS is capable of starting on battery (battery start).
Status Indicators: Fault, Utility, Battery There are three (3) status indicators on the front of the UPS (Utility, Battery and Fault), as shown in the diagram below. Each indicator illuminates to specify the status of the UPS (see Troubleshooting section for details). Utility Indicator (Green) The Utility Indicator illuminates green when the UPS is operating and supplying power to connected loads.
Site Wiring Fault Indicator (Red) The Site Wiring Fault Indicator on the rear panel, as shown below, illuminates red when the UPS detects a line-neutral reversal or a poor neutral-ground. (Refer to Troubleshooting Chart if this indicator is illuminated.
MODES OF OPERATION Normal Mode During Normal mode operation, the PowerSure PSP supplies conditioned, computer-grade power to the connected equipment: utility power passes through the EMI/RFI filters and TVSS circuitry and then through the Transfer Switch to the connected equipment. When the UPS is in Normal mode, the Utility Indicator illuminates green. Utility Indicator (Green) The PowerSure PSP continuously monitors the batteries to maintain them in a fully charged state.
Battery Mode The UPS switches to Battery mode in the event of an extreme voltage/ frequency condition or complete utility failure. The battery system supplies power through the Inverter to generate power for the connected equipment. When the UPS is in Battery mode, the Battery Indicator illuminates green and an alarm sounds every 10 seconds. Battery Indicator (Green) When a low battery condition occurs, the Battery Indicator changes to flashing amber and the alarm sounds every half-second.
COMMUNICATIONS DB-9 Connector The UPS has a DB-9 (9 pin female) connector on the rear to allow UPS status communications with a computer system running MultiLink™ software. The DB-9 is capable of supplying serial communication, on battery and low battery signals. MultiLink, Liebert’s UPS monitoring and shutdown software, is shipped with the UPS, along with a 10-ft. (3m) DB-9 cable required for running MultiLink.
Remote Shutdown Via the DB-9 Connector The PowerSure PSP can be shut down remotely by shorting Pins 5 and 6 or via Pins 4 and 5 of the DB-9 connector. Shutdown Via Pins 5 & 6 When Pin 6 is shorted to Pin 5, the UPS output is shut off regardless of what mode the UPS is operating in. The UPS cannot be started as long as the pins are shorted. When the short is removed, the UPS output can be enabled by pressing the ON/OFF/Alarm Silence button.
MAINTENANCE The PowerSure PSP UPS requires very little maintenance. Follow these practices to prevent problems. Cleaning the UPS The following will help ensure trouble-free operation for years: • Vacuum dust from the ventilation intake occasionally. • Wipe the cover periodically with a dry cloth. Maintaining Batteries The batteries are valve-regulated, nonspillable, lead acid and must be kept charged to retain their design life.
Battery Replacement Procedure Replacement requires removing the battery cover plate on the bottom of the UPS. No tools are needed. To replace the batteries: 2. Pull the white tab towards you to remove the battery from the UPS. Pivot battery 90 degrees clockwise as shown below. 1. Remove the battery cover plate on the bottom of the UPS. Side view of UPS Bottom view of UPS 4. Insert a new battery pack, and push the connectors onto the battery terminals (black to black & red to red). 3.
TROUBLESHOOTING The information below indicates various symptoms a user may encounter in the event the PowerSure PSP experiences a problem. Use this information to determine whether external factors caused the problem. See Troubleshooting Chart for suggested remedy. 1. The Fault indicator illuminates, indicating the Utility UPS detected a problem. Indicator Fault Battery 2. An alarm sounds, alerting that the UPS requires attention.
Troubleshooting Chart If the UPS fails to operate properly, turn off the unit and repeat the steps in the Installation section of this manual. If the problem persists, refer to the chart below: Problem UPS will not start UPS starts on battery, but will not switch to AC Cause Overload/Short Circuit Check the circuit protector on the rear of the UPS. If it is tripped, reset it and restart the UPS. For further help, call your local dealer, Liebert representative or the Liebert Worldwide Support Group.
SPECIFICATIONS Model Number PSP350MT-120 PSP500MT-120 PSP650MT-120 350VA/210W 500VA/300W 650VA/390W 3.7 x 9.5 x 8 (95 x 240 x 205) 6.7 x 13.1 x 11.5 (171 x 332 x 293) 3.7 x 9.5 x 8 (95 x 240 x 205) 6.7 x 13.1 x 11.5 (171 x 332 x 293) 3.7 x 9.5 x 8 (95 x 240 x 205) 6.7 x 13.1 x 11.5 (171 x 332 x 293) 10.2 (4.6) 12.6 (5.7) 10.2 (4.6) 12.6 (5.7) 10.2 (4.6) 12.6 (5.7) Power Rating VA/W DIMENSIONS: in.
AGENCY Safety UL 1778, c-UL Listed ANSI C62.
24
SIDE VIEW OF POWERSURE PSP 1.38" (35 mm) Bottom of UPS Remove this template from the user manual. Line template up to wall at desired location. Drill holes where cross hairs are located on template. Remove template and mount screws, using (3) #8 or M4 screws. (Distance from head of screw to wall should be 0.25" or 6.4mm.) 5. Mount PowerSure PSP to wall. 1. 2. 3. 4. PowerSure PSP Mounting Template 5.12" (130 mm) 3.49" (88.
POWER AVAILABILITY POWERSURE™ PSP The Company Behind the Products With over a million installations around the globe, Liebert is the world leader in computer protection systems.