PowerSure™ PS250-50S PS400-50S PS600-50S 250 VA 400 VA 600 VA POWER PROTECTION Uninterruptible Power System 250 VA – 600 VA 230 VAC USER’S MANUAL R
IMPORTANT SAFETY INSTRUCTIONS WARNING: Do not attempt to service this product yourself except to replace the battery. Opening or removing the cover may expose you to dangerous voltages, even when the AC cord is disconnected from the electrical outlet. Refer all servicing to qualified service personnel. 1. SAVE THESE INSTRUCTIONS. ADHERE TO ALL OPERATING INSTRUCTIONS AND WARNINGS ON THE UNIT AND IN THIS MANUAL. 2. This equipment is designed for Commercial/Industrial use only.
1. 2. 3. 4. 5. 6. 7. 8. 9. 10. ON/OFF Button Battery Light (400/600 Only) Check Light (400/600 Only) AC Light Battery Test Button (400/600 Only) Option Switches Output Receptacles Power Cord Input Circuit Breaker Communications Port ATTENTION: Please refer to these drawings when reading this manual. This manual references the various parts of your UPS by number. INSTALLATION INSTRUCTIONS 1. Unpack unit and check contents. There should be one UPS, two CEE-22 output cables, and one User's Manual.
5. After charging, shutdown both the UPS and load equipment and unplug them from the AC supply socket. Connect the supplied CEE-22 output cable (B) between the load equipment input socket (D) and one of the UPS AC output sockets (E). Connect all load equipment to UPS in this way. 6. When all equipment is plugged in, plug UPS into the AC supply socket and turn it ON. The UPS is ready for normal operation. OPERATING INSTRUCTIONS 1.
COMPUTER/LAN INTERFACE (400/600 VA ONLY) Optional SiteNet 1 kits provide connection to a wide range of popular computer operating systems; such as Novell, UNIX, UNISYS, SUN, WINDOWS and many others. SiteNet 1 software automatically performs an orderly shutdown of computer operating systems, in the event of a power outage and/or low battery conditions. The SiteNet 1 kit supplies a cable to connect supported computer systems to the UPS communications port (10). The table below shows connector details.
Option Switch 3 & 4: Low Voltage Limit Select – Low voltage limit is the voltage level at which battery operation starts. You may set the low voltage limit of the UPS to 180V, 190V, or 200V. The factory setting is 190V. This option reduces excessive battery usage in brownout conditions. Make sure your computer equipment can operate at 180 VAC before selecting the lowest limit (most will).
To Replace the Battery: 1. Close active programs and turn off computers. Turn OFF the UPS and unplug it from mains supply. 2. Place UPS on its side and remove retaining screws (A) to battery door (B). 3. Open battery door (B) and remove the battery (C) by pulling on the battery tab (D). 4. Remove terminal wires (E) from old battery. Connect terminal wires (E) to new battery (C); the red connects to the positive terminal, the black connects to the negative. DO NOT reverse terminal connections.
PROBLEM UPS will not start CAUSE SOLUTION Input voltage below threshold Wait until mains voltage rises to appropriate level. Overload/Short Circuit Check circuit breaker at rear of UPS (9). If it is activated, reset it and restart the UPS (See "Resetting Circuit Breaker'). If problem persists, disconnect some of the equipment from UPS - the total wattage or all your equipment may exceed the capacity of the UPS. If it still will not start, check your computer equipment for short circuits.
250 VA LED & ALARM INDICATIONS Condition NORMAL/START UP Start-Up Test Fail Input Frequency Mismatch with Option Switch Setting Green AC Light (4) On after Beep On after Beep Input Voltage Below Threshold Overload/Short Circuit NORMAL MODE Battery Test Fail Overload/Short Circuit BACKUP MODE Low Battery Alarm Low Battery Shutdown Main Overvoltage (transfer enabled) Audible Alarm Status Single Beep, then Off Fast Beep for 15 Sec and then Off Operate Operate Off Continuous Will Not Start Off On On O
SPECIFICATIONS Model # / Stock # Model Rating Dimensions: mm Unit (W x D x H) Shipping (W x D x H) Weight: Kg Unit Shipping AC Parameters Receptacles Input Voltage Range Low Voltage Transfer Point High Voltage Transfer Point Input Frequency Range Spike Protection Output Voltage (on battery) Output waveform (on battery) Max. Output Current at 230 V Output Frequency Max.
LIMITED WARRANTY Liebert Corporation extends the following LIMITED WARRANTY to the purchaser and to its customer (collectively referred to as the "Purchaser"): the enclosed Uninterruptible Power System (UPS) and components are free from defects in materials and workmanship under normal use, service, and maintenance FOR A PERIOD OF TWO YEARS FROM THE DATE OF ORIGINAL PURCHASE from Liebert or the Liebert dealer or retailer.
R 1050 Dearborn Drive Columbus, OH 43229 614-888-0246 Technical Support U.S.A................................................................ 1-800-222-5877 Outside the U.S.A ........................................... 614-841-6755 U.K................................................................ +44 (0) 1793 553355 France ...........................................................+33 1 4 87 51 52 Germany ...................................................... +49 89 99 19 220 Italy ....................