NO. OF EBCS
LOAD
PERCENTAGE
OF CAPACITY
750VA 1000VA 1500VA 2000VA 3000VA
+3 EBC
10% 1032.5 820.5 783.5 603.5 632.5
20% 578 443 409 306.5 318
30% 396 297.5 271 199.5 207
40% 297.5 220.5 199.5 144 148.5
50% 236 172.5 155.5 113.5 116.5
60% 194 140 127 94 96
70% 163.5 119 108 79.5 81.5
80% 140 104 94 69 70.5
90% 123.5 92.5 82.5 60.5 61.5
100% 111 82.5 74 54 54.5
+4 EBC
10% 1338.5 1066 1018 786.5 824
20% 754 580.5 537 404.5 419.5
30% 519.5 393.5 359.5 267 277
40% 393.5 294 267 196 202
50% 314.5 232.5 210.5 152 156
60% 260 191 172 124 127
70% 221 160.5 143.5 105.5 108
80% 191 137.5 124 91.5 94
90% 167.5 122 109.5 81 82.5
100% 148.5 109 98 72 73
+5 EBC
10% 1644 1311 1252.5 969,5 1015.5
20% 930 718 664.5 503 521
30% 643.5 489 447.5 335 347
40% 489 368 335 248 255
50% 392.5 292.5 265.5 194.5 199.5
60% 326.5 241.5 219 157.5 162
70% 278 204.5 184 131.5 135
80% 241.5 176.5 157.5 114.5 117
90% 213 154.5 137 101 103
100% 190 136.5 122.5 90.5 92
Table 7.5 Battery Run Time in Minutes (continued)