NO. OF EBCS
LOAD
PERCENTAGE
OF CAPACITY
750VA 1000VA 1500VA 2000VA 3000VA
0
(UPS only)
10% 118 92.5 88 66.5 70
20% 63.5 47 42.5 30 31.5
30% 41 29 25.5 17.5 18.5
40% 29 20 17.5 12 12.5
50% 21.5 15 13 9 9
60% 17 11.5 10.5 7 7
70% 14 9.5 8.5 5.5 6
80% 11.5 8 7 4.5 4.5
90% 10 7 6 3.5 4
100% 8.5 6 5 3 3
+1 EBC
10% 421 330 314 237 249.5
20% 226 168.5 154 113.5 117.5
30% 148 110.5 100.5 74.5 77.5
40% 110.5 82.5 74.5 55 56.5
50% 88 65 59 42 43.5
60% 73 53.5 48 33.5 34.5
70% 62 44.5 39.5 27.5 28
80% 53.5 38 33.5 23 23.5
90% 46.5 33 28.5 19.5 20
100% 41 28.5 25 17 17
+2 EBC
10% 727 575.5 549 420 441
20% 402 305.5 281.5 208 216.5
30% 272 201.5 183 132 137
40% 201.5 146.5 132 98.5 101.5
50% 158 116 105.5 78 80
60% 128.5 96 87.5 64 65.5
70% 110 82 74 54 55.5
80% 96 71 64 46 47
90% 85 63 56 40 40.5
100% 76 56 49.5 35 35.5
Table 7.5 Battery Run Time in Minutes