User Manual
Table Of Contents
- Important Safety Information
- 1 GXT5 Description
- 2 Installation
- 3 Operating the UPS
- 4 Operation and Display Panel
- 5 Maintenance
- 6 Troubleshooting
- 7 Specifications
- Appendices
MODEL NUMBER: GXT5- EBC36VRT2U EBC36VRT2UE EBC48VRT2U EBC48VRT2UE EBC72VRT2U EBC72VRT2U
USED W/UPS MODEL: 750 – 1,000 VA 1,500 – 2,000 VA 3,000 VA
Dimensions, D×W×H, in.(mm)
Unit
14.6 x 16.9 x 3.3
(370 × 430 × 85)
19.7 x 16.9 x 3.3
(49 7 × 430 × 85)
23.7 x 16.9 x 3.3
(602 × 430 × 85)
Shipping 24.3 x 22.4 x 10.3 (617 x 570 x 262)
28.2x224x10.3
(717x570x262)
Weight, lb.(Kg)
Unit 49.72 (22.6) 63.36 (28.8) 90.64 (41.2)
Shipping 63.14 (28.7) 57.86 (26.3) 77 (35) 71.72 (32.6) 104.72 (47.6) 99.22 (45.1)
Battery
Type Valve-regulated, non-spillable, lead acid
Qty×V×Rating 2×3 × 12V × 9.0Ah 2×4 × 12V × 9.0Ah 2×6 × 12V × 9.0Ah
Battery Mfr./Part# LEOCH/DJW12-9.0
Backup time See Battery Run Times below.
EnvironmentalRequirements
Operating Temperature,
°F (°C)
32 to 104 (0 to 40)
Storage Temperature, °F
(°C)
5 to 104 (-15 to 40) High ambient temperatures will reduce battery life
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to 10,000 ft. (3000m) at 77ºF (25ºC) without derating
Agency
Safety
EN 62040-1:2008+A1:2013;
GS mark;
UL 1778 5th Edition and CSA 22.2 No. 107.1
EMC
EN 62040-2:2006
EN 61000-3-2:2014
EN 61000-3-3:2013
Safety UL 1778 5th Edition and CSA 22.2 No. 107.1
Transportation ISTA Procedure 1A
Surge Immunity ANSI C62.41 Category B
RFI/EMI FCC Part 15 (Class A)
Table 7.4 External Battery Cabinet Specifications
7.1 Battery Run Times
NOTE: Run times in this table are approximate. Times are based on new, fully-charged, standard
battery modules at a temperature of 77°F (25°C) with 100% resistive UPS loading. Run times listed
above can vary by ±5% due to manufacturing variances of the individual batteries.
7 Specifications
63