User Manual
Table Of Contents
- Important Safety Information
- 1 GXT5 Description
- 2 Installation
- 3 Operating the UPS
- 4 Operation and Display Panel
- 5 Maintenance
- 6 Troubleshooting
- 7 Specifications
- Appendices
MODEL GXT5- 3000IRT2UXL 3000IRT2UXLE 3KL620RT2UXL 3KL630RT2UXL
RATING 3000VA/3000W 3000VA/2700W 3000VA/3000W
Dimensions, D×W×H, in.(mm)
Unit 21.3 x 16.9 x 3.4(540 × 430 × 85)
Shipping 28.2 x 22.4 x 10.3(717 x 570 x 262)
Weight, lb.(Kg)
Unit 62 (28.2) 65.1 (29.6) 67.1 (30.5)
Shipping 79.2 (36) 72.6 (33) 79.2 (36) 80.5 (36.6)
Input AC
Voltage Range
(typical)
230VAC nominal; variable based on output load 208VAC nominal; variable based on output load
90%~ 100%
loading
184~ 196VAC/288VAC 182~ 191VAC/288VAC
70%~ 90%
loading
161 ~184VAC/288VAC 164 ~182VAC/288VAC
28%~ 70%
loading
115~ 161VAC/288VAC 129~ 164VAC/288VAC
0~ 28% loading 115VAC/288VAC 129VAC/288VAC
Frequency 40Hz ~ 70Hz; Auto Sensing
Input Power Cord C20 L6-20P L6-30P
Output AC
Output
Receptacles
C13×6&C19 L6-20R×2&L6-15R*2 L6-30R×2&L6-15R*2
Voltage 200/208/220/230/240VAC (user-configurable); ±3% 208VAC;±3%
Waveform Sine wave
Utility(AC) Model
Overload
>200% for 250ms; 150- 200% for 2 seconds; 125- 150%
for 50 seconds; 105-125% 60 seconds;
>200% for 250ms; 150- 200% for 2 seconds; 125-
150% for 10 seconds; 105-125% 15 seconds;
Internal Charger
Charging current Nominal 2.2 A; Maximum 8A
Battery
Type Valve-regulated, non-spillable, lead acid
Qty×V×Rating 6 × 12V × 9.0Ah
Battery
Mfr./Part#
LEOCH/DJW12-9.0
Backup time See Battery Run Times on page63.
Recharge Time 3 Hours to 90% capacity after full discharge with 100% load till UPS auto-shutdown (Internal Batteries Only)
Table 7.3 UPS Specifications, 3000VA Models
7 Specifications