User Manual

Table Of Contents
MODEL GXT5- 1500IRT2UXL 1500IRT2UXLE 2000IRT2UXL 2000IRT2UXLE
RATING 1500VA/1500W 1000VA/1000W
Dimensions, D×W×H, in.(mm)
Unit 18.5×16.9×3.4(470×430×85)
Shipping 24.3 ×22.4 x 10.3(617 x 570 x 262)
Weight, lb.(kg)
Unit 46.2 (21)
Shipping 61.6 (28) 56.1 (25.5) 61.6 (28) 56.1 (25.5)
Input AC
Voltage Range(typical) 230VAC nominal; variable based on output load
90% 100% loading 168~ 177VAC/288VAC
70% 90% loading 150 ~168VAC/288VAC
28% 70% loading 115~ 150VAC/288VAC
0 28% loading 115VAC/288VAC
Frequency 40Hz ~ 70Hz; Auto Sensing
Input Power Cord C14 C20
Output AC
Output Receptacles C13×8
Voltage 200/208/220/230/240VAC (user-configurable); ±3%
Waveform Sine wave
Utility(AC) Model
Overload
>200% for 250ms; 150- 200% for 2 seconds; 125- 150% for 50 seconds; 105-125% 60 seconds;
Internal Charger
Charging current Nominal 2.2 A; Maximum 8A
Battery
Type Valve-regulated, non-spillable, lead acid
Qty×V×Rating 4 × 12V × 9.0Ah
Battery Mfr./Part# LEOCH/DJW12-9.0
Backup time See Battery Run Times on page63.
Recharge Time ) 4 Hours to 90% capacity after full discharge with 100% load till UPS auto-shutdown (Internal Batteries Only
EnvironmentalRequirements
Operating
Temperature, °F (°C)
+32 to +122 (0 to 50); Operating temperature may be increased to 122°F (50°C with a 10% de-rating of the
output power
Storage Temperature,
°F (°C)
-4to +140 (-20 to 60)( contain batteries will be from -15 to 40°C.)
Table 7.2 UPS Specifications, 1500VA and 2000VA Models
7 Specifications
59