User Manual
Table Of Contents
- Important Safety Information
- 1 GXT5 Description
- 2 Installation
- 3 Operating the UPS
- 4 Operation and Display Panel
- 5 Maintenance
- 6 Troubleshooting
- 7 Specifications
- Appendices
7 SPECIFICATIONS
MODEL GXT5- 750IRT2UXL 750IRT2UXLE 1000IRT2UXL 1000IRT2UXLE
RATING 750VA/750W 1000VA/1000W
Dimensions, D×W×H, in.(mm)
Unit 15.7 x 16.9 x 3.4 (400 x 430 x 85)
Shipping 24.3 x 22.4 x 10.3 (617 x 570 x 262)
Weight, lb.(kg)
Unit 36.3 (16.5)
Shipping 51.7 (23.5) 46.2 (21) 51.7 (23.5) 46.2 (21)
Input AC
Voltage Range(typical) 230VAC nominal; variable based on output load
90%~ 100% loading 168~ 177VAC/288VAC
70%~ 90% loading 150 ~168VAC/288VAC
28%~ 70% loading 115~ 150VAC/288VAC
0~ 28% loading 115VAC/288VAC
Frequency 40Hz ~ 70Hz; Auto Sensing
Input Power Cord C14
Output AC
Output Receptacles C13×8
Voltage 200/208/220/230/240VAC (user-configurable); ±3%
Waveform Sine wave
Utility(AC) Model Overload >200% for 250ms; 150- 200% for 2 seconds; 125- 150% for 50 seconds; 105-125% 60 seconds;
Internal Charger
Charging current Nominal 2.2 A; Maximum 8A
Battery
Type Valve-regulated, non-spillable, lead acid
Qty×V×Rating 3 × 12V × 9.0Ah
Battery Mfr./Part# LEOCH/DJW12-9.0
Backup time See Battery Run Times on page63.
Recharge Time
3 Hours to 90% capacity after full discharge with 100% load till UPS auto-shutdown (Internal Batteries
Only)
EnvironmentalRequirements
Table 7.1 UPS Specifications, 750VA and 1000 VA models
7 Specifications
57