8. Activate the new battery pack(s) using the operating/display panel:
NOTE: The display menus and functions are described in Operation and Display Panel on page29.
From the main menu, select Settings, then the Monitoring tab and verify that the date
and time are correct. If the date or time need correction, see Setting the Date and Time
on page49.
Select the Battery tab, use the arrows to select Replace Battery, and press Enter.
The replaced battery packs are activated.
Use ESC to return to the main display.
Figure 5.1 Replacing the Battery Pack
ITEM DESCRIPTION
1 Battery pack
2 Battery door
3 Front panel
5.2 Charging Batteries
The batteries are valve-regulated, non-spillable, lead acid and should be kept charged to attain their
design life. The UPS charges the batteries continuously when it is connected to the utility input power.
If the UPS will be stored for a long time, We recommend connecting the UPS to input power for at least 24
hours every 4 to 6months to ensure full recharge of the batteries.