MESSAGE DESCRIPTION
Remote shut-
off
Remotely power off
Remote
shutdown
Dry contact activated at any mode shutdown
REPO Shutdown caused by the REPO terminal Normally Closed contact open
Restore factory
defaults
Under UPS stand-by state, set 'Restore Factory Defaults' function via the Maintain page
Shutdown due
to overtemp
During the UPS operation, the system checks that the heat sink temperature exceeds the setting range.
If overtemperature, please check:
1. Ambient temperature too high or not
2. Dust is blocked or not
3. Fan fault or not
System fault Alarm when model configuration is incorrect. Contact Vertiv Technical support.
System
overtemp
Internal heat sink temperature too high, and the inverter is off. The alarm can only be silenced if the heat-sink
temperature is lower than the alarm setting. The system can automatically start after overtemperature fault is
solved.
If overtemperature, please check:
1. Ambient temperature too high or not
2. Dust is blocked or not
3. Fan fault or not
Turn off
programmable
outlet
The programmable-outlet status changed from "Turn On" to "Turn Off"
Turn on fail
The UPSdoes not start because there is no mains/utility power or it is greater than the voltage required to supply
the full load. Check the AC input power.
Turn on
programmable
outlet.
The programmable-outlet status changed from "Turn Off" to "Turn On."
UPS has no
output
Both Inverter and Bypass provide no power supply.
UPS is out of
service
The UPS is out of service.
Table 4.4 Alarm Messages (continued)
About Screen
The About screen offers tabs that list information about the product and the network. The Efficiency tab
shows a chart of battery efficiency versus capacity. The Battery age tab show a chart of SOHpercentage
versus battery age in years.
To view the product and network information:
1. At the main menu, select the About icon, and press
Enter.
4 Operation and Display Panel