User Manual
Table Of Contents
- Important Safety Information
- 1 GXT5 Description
- 2 Installation
- 3 Operating the UPS
- 4 Operation and Display Panel
- 5 Maintenance
- 6 Troubleshooting
- 7 Specifications
- Appendices
ITsystem compatibility
Enables/Disables the neutral back-feed relay on battery mode.
Outlet parameter options
Apply the same settings across outlets
Applies the settings for another outlet to this outlet. This lets you set the parameters for a single
outlet and apply identical settings to multiple outlets at once.
Turn on outlet
Turns-on the outlet.
Turn on delay
Length of time to elapse before outlet turns on after UPS start-up.
Turn off when UPS overloads
Enables/Disables turning-off the outlet if the UPS is overloaded.
Outlet settings based on discharging time
Threshold of turning off the outlet
Length of time that the batteries discharge before turning off the outlet.
Turn on when power returns
Length of time to elapse after input power returns before turning on the outlet.
Outlet settings based on backup time
Threshold of turning off the outlet
Amount of back-up time remaining to turn off the outlet.
Turn on when power returns
Length of time to elapse after input power returns before turning on the outlet.
Outlet settings based on capacity
Threshold of turning off the outlet
Percent capacity remaining to turn off the outlet.
Turn on when power returns
Length of time to elapse after input power returns before turning on the outlet.