Bypass voltage lower limit
Percentage that the input voltage may be below the selected output voltage setting and remain in
Bypass mode.
Run mode
Selects Normal or ECO operation for the UPS. Options are:
Normal = Connected load is always powered through the UPS inverter. ECO mode is disabled.
ECO mode = ECOmode is enabled. The UPS inverter is bypassed, and the connected load is
powered by utility/mains power within the selected ECOvoltage and frequency tolerances.
Battery parameter options
External battery AH
Sets the Amp-hour.
External battery cabinet group No.
Sets the number of external battery cabinets.
Low battery time
Sounds an alarm when the selected amount of time remaining for the UPS to operate in Battery
mode is met.
Battery periodic test enable
Enables/Disables automatic battery self test.
Batt. note duration (month)
Sets the duration of the notice to replace the batteries.
Dischg protect time
Sets the discharge protection time.
Equal charge enable
Enable/Disabels equal-charge mode.
Max chg curr
Sets the maximum charge current.
Temp compensation
Enables/Disables temperature compensation.
Replace battery
Activates newly-installed battery packs after replacement.