Settings Submenu
The settings screen consists of tabs that list UPS settings for configuration and adjusting parameters
with tabs for:
Output
Battery
Monitor
System
Outlets
NOTE: Do not change parameter settings or reset to factory defaults when powering-off the UPS.
To modify UPSsettings:
1. At the main menu, select the Settings icon, and press Enter.
NOTE: To adjust the settings, you must enter a password. See Editing Display and Operation Settings
on page47, for details on entering the password and editing the setting parameters.
2. Use the arrow buttons to move the cursor left/right and select a tab, then press Enter to
display the parameter list for the selected tab.
Output parameter options
Voltage selection
Selects the default output voltage.
Startup on bypass
Whenenabled, the UPS starts in Bypass mode then transfers to Normal mode. When disabled, the
UPS starts in Normal mode.
Frequency selection
Selects the frequency of the output. Options are:
Auto, Bypass enabled = Automatically detects frequency of utility/mains power and sets the
nominal frequency to match and bypass mode is enabled. Typical operating mode.
Auto, Bypass disabled = Automatically detects frequency of utility/mains power and sets the
nominal frequency to match and bypass mode is disabled.
Frequency converter 50Hz = Bypass mode is disabled and the UPSprovides 50-Hz output
from any qualified utility/mains power.
Frequency converter 60Hz = Bypass mode is disabled and the UPSprovides 60-Hz output
from any qualified utility/mains power.
Bypass voltage upper limit
Percentage that the input voltage may be above the selected output voltage setting and remain in
Bypass mode.