Install Instructions

©Copyright 2011 Liberty Pumps Inc. All rights reserved 2
IMPORTANT: All Liberty Pump models are supplied with their own separate Installation/Operation/Maintenance
manuals. Ensure that you have received these manuals, and that you read and understand them prior to installing this
unit. If you have any questions, call Liberty Pumps customer service at (800) 543-2550.
GR22 and GR30 Assembly
The GR22 or GR30 quick disconnect assembly provides easy installation and
removal of the pump. When installed correctly it will seal and provide support
for the pump. Please ensure that installation is done as per the diagrams
below.
The rail system comes in three parts:
1) Base: This is the large casting that is mounted to the floor of the
pumping chamber or vault. ½” studs are recommended spaced at 5.5”
apart.
2) Pump mounting claw: Liberty offers three different pump mounting
claws. The LE claw and GR30 claw have a larger flange and fits
LE70-Series, LE100-Series, LEH100-Series, LEH150-Series and
LEH200-Series sewage pumps. The FL claw mates to FL100-Series,
FL150-Series and FL200-Series effluent pumps. Both GR22-LE and
GR22-FL claws are threaded 2” FNPT for optional mounting
applications. The GR22-S claw has a 2 NPT male thread for pumps
with threaded discharges.
3) Support bracket: A small casting is supplied and is used to support
the top end of the 1-1/4” guide rail pipe (pipe not included). This
casting needs to be mounted to a support structure, bar stock, angle
iron, or other means that attaches to the side walls of the vault. Note,
heavy guide rail pipe 1-1/4” Galvanized or Stainless Steel is
recommended.
All the claws have a sealing grommet attached to it that provides the seal
between the claw and base unit. This seal requires no maintenance. On
GR30, GR22-LE, AND GR22-FL a gasket should be used between the claw
and pump the gasket and mounting hardware are provided with the
pump. The stock flange that is shipped with the pump should be removed and
replaced with the claw.
The GR22-S features a split design for
pumps without a flange. The threaded
base can be screwed into the pump’s
discharge and then the claw and
gasket can be mounted.