Installation
Water Quality
The standards for adding water quality
Index
PH[25°C] 6.5~8.0
Electric conductivity[25°C](µs/cm) Below 200
Chloride ion(mgCl-/L) Below 50
Sulfate ion (mgSO4
2-
/L) Below 50
Acid consumption[PH4.8](mgCaCO3/L) Below 50
Calcium hardness(mgCaCO3/L) Below 50
Turbidity Below 50
Fe(mgFe/L) Below 50
Ammonium ion(mgNH4
+
/L) Below 50
Ionic phases silica(mgSiO2/L) Below 50
Item Standards
Standard Item
Reference Item
Circuit Breaker
Air
Conditioner
Main power source
Circuit Breaker
Use a circuit breake
or time delay fuse.
Use a recognized circuit breaker between the power source and the unit.
A disconnecting device to adequately disconnect all supply lines must be fitted.
Capacity of the Circuit Breaker must lie between MCA and MOP
- MCA = 1.25 x Current of Motor
- MOP = 2.25 x Current of Motor
Fan Coil Unit
20