User manual
Installation Manual 15
Installation
Pipe Connect, Insulation
Water pipe Connection and Insulation
All thermal insulation must comply with local requirement the thickness min 20mm.
Make sure that there is no clearance here.
Overlap with thermal
insulator for piping.
Thermal insulator for water pipe
(Local supply)
Thermal insulator for
piping(Local supply)
Hose clip for thermal insulator(Local supply)
Union for water pipe
Water valve
insulator(Local supply)
Elbow pipe
(Local supply)
Use a spanner to tignten the water pipe. Make sure, the pipe is
tightened firmly
Drainage hole Make sure to be closed
Unit
Drainage pipe
(Local supply)
Thermal insulator
(Local supply)
Ceiling Suspended
Lay the drain hose with a downward inclination so water will drain out.
• Always lay the drain with downward inclination
(1/50 to 1/100).
Prevent any upward flow or reverse flow in any
part.
• 10mm or thicker formed thermal insulator shall
always be provided for the drain pipe.
INCORRECT
CORRECT
Drain piping work
Clip
(Local supply)
Drain pipe
Ceiling Suspended 1/2"
Floor Standing 3/4"