User manual
Hang the Fan Coil unit on suspension bolt as per following guidelines:
1. Lift the fan coil unit to sufficient height.
2. Insert the suspended part of four suspension bolt in the four hangers provided on the side of
main body one by one.
3. Lower the fan coil unit till the hangers rest on their respective flat washer.
4. Adjust the level in the top down direction by adjusting the suspension bolts.
Inclined the fan coil unit as per direction provided in the fig
Installation
1. Install declination of the fan coil unit is very important for the drain of the
decorative type air conditioner.
2. Minimum thickness of the insulation for the connecting pipe shall be 10mm.
3. If the Installation Plates are fixed to horizontal line, the fan coil unit after installing will
be declined to the bottomside.
Front of view
The unit must be horizontal or inclined at angle.
The inclination should be less than or equal to 1 or in between 10 to 20mm inclined in drain
direction as shown in fig.
The unit must be declined to the bottomside of the unit when finished installation.
Side of view
: Installation Information For Declination
Drain hose
10~20mm
Ceiling
Ceiling
10~20mm
Ceiling
5~10mm
Fan coil unit installation
•
•
°
•
14
Fan Coil Unit