Owner's Manual
12
THE INDOOR UNIT INSTALLATION
ENGLISH
C
E
G
D
F
I
A
J
B
H
Drainage hole
Dimension
Capacity (kBtu/h)
A B C D E F G H I J
Low
Static
9 733 772 628 700 36 190 20 660 155 700
12/18 933 972 628 700 36 190 20 860 155 900
24 1 133 1 172 628 700 36 190 20 1 060 155 1 100
Mid
Static
18/24/30 933.4 971.6 619.2 700 30 270 15.2 858 201.4 900
36/42 1 283.4 1 321.6 619.2 689.6 30 270 15.2 1 208 201.4 1 250
48/60 1 283.4 1 321.6 619.2 689.6 30 360 15.2 1 208 291.4 1 250
(Unit: mm)
M10 Nut
M10 SP. washer
M10 washer
X 4
X 4
(Local
supply)
X 4
M10 Nut
M10 SP. washer
M10 washer
X 4
X 4
(Local
supply)
X 4
1 Set anchor
Old building New building
2 Plate washer
3 Spring washer
4 Nut
5 Suspension
bolts
• Local supply
① Set anchor
② Plate washer - M10
③ Spring washer - M10
④ Nut - W3/8 or M10
⑤ Suspension bolt - W3/8 or M10
* The feature can be changed according to
type of model.
Position of suspension Bolt
- Apply a joint-canvas between the unit and
duct to absorb unnecessary vibration.
- Apply a filter Accessory at air return hole.
Position of console Bolt
- Insert the set anchor and washer onto the
suspension bolts for locking the suspension
bolts on the ceiling.
- Mount the suspension bolts to the set
anchor firmly.
- Secure the installation plates onto the
suspension bolts (adjust level roughly) using
nuts, washers and spring washers.