Spec Sheet
CYRWGlGhOb
> Connects to the HVAC unit using
standard thermostat wiring
Wiring Table - 24V AC
Wire
Color
Terminal
Letter
Terminal
Connection
BLACK C COMMON
RED R 24V
YELLOW Y COMPRESSOR
WHITE W HEAT
ORANGE O or B REVERSE VALVE
GREEN GH FAN HIGH
PURPLE GL FAN LOW
Wiring Table - 24V DC
Wire
Color
Terminal
Letter
Terminal
Connection
BLACK R 24V
RED C COMMON
YELLOW Y COMPRESSOR
WHITE W HEAT
ORANGE O or B REVERSE VALVE
GREEN GH FAN HIGH
PURPLE GL FAN LOW
Thermostat
Case Dimensions (Imperial)
4.02 x 5.51” x 0.93”
Case Dimensions (Metric)
102mm x 140mm x 23.5mm
Screen Dimensions (Imperial)
3.63” x 2.13”
Screen Dimensions (Metric)
92mm x 54mm
Operating Voltage
24V AC/DC
Control Outputs
Fan High (GH)
Fan Low (GL)
Compressor (Y)
Heat Pump (OB)
Heat (W)
Occupancy Sensor Beam Width
±47° (94°)
Wireless Frequency 900MHz
Temperature Accuracy ±1°F
FCC ID XEYWX
IC 8410A-WX
> Easy-to-use Thermostat
> Unparalleled Energy Savings
> Uncompromising Guest Comfort
> Quick-and-Easy Installation
> Remote Management Capabilities*
The Verdant VX Series Thermostat delivers unprecedented
energy savings without compromising guest comfort.
An Integrated occupancy sensor allows for energy saving when
rooms are unoccupied.
Energy saving presets eliminate guesswork and make it easy to
adjust the energy saving settings.
A patented “Night Occupancy” feature ensures comfort while
guests are sleeping.
Built-in wireless mesh-networking enables optional remote
management features.
Fully configurable settings allow for customization of energy
savings to fit any situation.
Temperature Setback automatically adjusts the temperature
when rooms are unoccupied to save energy.
Temperature Recovery allows for setting a maximum time
permitted for establishing a comfortable room temperature.
Setback Optimization monitors the temperature recovery
rate and optimizes setback temperatures.
Setback Limits control the maximum and minimum room
temperature when a room is in setback mode.
Set Point Limits prevent guests from setting the room
temperature to extreme, energy-wasting levels.
US PATENTS: 8,369,994; 8,141,791; 7,918,406; 7,841,542; 7,838,803; RE40,437; 7,232,075; 7,185,825; 7,156,318;
7,152,806; 7,145,110; 7,058,477; 7,050,026; 7,028,912; 6,902,117; 6,789,739; 6,786,421; 6,619,555; 6,581,846; 6,578,770;
CANADIAN PATENTS: CA2615065; CA2633113; CA2633121; CA2633200; OTHER PATENTS PENDING.
Verdant Environmental Technologies, Inc. reserves the right to make changes, without notice, in design or components
as progress in engineering and manufacturing methods may warrant. Product appearance may vary.
© Verdant Environmental Technologies, Inc. 2017
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT TO THE
FOLLOWING TWO CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE,
AND (2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE
THAT MAY CAUSE UNDESIRED OPERATION.
PURSUANT TO PART 15.21 OF THE FCC RULES, ANY CHANGES OR MODIFICATIONS TO THIS
EQUIPMENT NOT EXPRESSLY APPROVED BY VERDANT ENVIRONMENTAL TECHNOLOGIES, INC.
MAY VOID VOID THE USER’S AUTHORITY TO OPERATE THE EQUIPMENT.
Verdant Environmental Technologies, Inc. • 1850 55th Avenue, Montreal, QC, Canada, H8T 3J5 • TEL: 514.344.4448 • FAX: 514.344.5977 • EMAIL: sales@verdant.info
* Requires an optional “Online Connection Kit” (Part Number: V8-OL-KT) and a service subscription. Additional fees apply.