Owner's Manual
10
INSTALLING THE INTERNET BRIDGE
ENGLISH
Note : Indoor unit address setting completed site
- The site that already completed the indoor unit address does not require address setting
again.
Note : How to set the indoor unit’s central control address
- According to the indoor unit product or the type of the remote controller, the methods of
setting the central control address may be different, so refer to the indoor unit product or
wired remote controller manual for the address setting.
Note : Assignment of outdoor unit and indoor unit number
- If the outdoor unit product is Multi V, it is recommended to set the first digit of the address
with outdoor unit number, and set the second digit with indoor unit number, so that the sys-
tem composition and division can be easily identified during the address setting.
Indoor unit address setting
The addresses of the indoor units connected to one internet bridge shall be assigned without
overlapping. You can set the indoor unit address as hexadecimal 00 ~ FF.
The following is an example of assigning addresses to the indoor unit.
Outdoor unit (group) number Indoor unit number
i@b
Multi V
Multi V
Ventilation device
Ventilation device
PI485
PI485
PI485