LG VRF Systems
33 34
LG Air Conditioning Technologies
Specifications Unit ARWN192BAS4 ARWB216BAS4 ARWB288BAS4
Frames
ARWN072BAS4
ARWN121BAS4
ARWB072BAS4
ARWB144BAS4
ARWB144BAS4
ARWB144BAS4
Tons 16 18 24
Nominal Capacity
Cooling
1
Btu/h 192,000 216,000 288,000
Heating
1
Btu/h 216,000 243,000 324,000
Rated Capacity
Cooling
2
Btu/h 184,000 206,000 274,000
Heating
2
Btu/h 206,000 232,000 308,000
Power Voltage V / Hz / ø 208-230/60/3 208-230/60/3 208-230/60/3
Power/Communication Wiring No x AWG 2 x 18 2 x 18 2 x 18
Dimensions (W×D×H) Body in 63-1/2x39-1/4x19-3/4 29-3/4x39-1/4x19-3/4 29-3/4x39-1/4x19-3/4
Weight
Net lbs 280 x 2 280 x 2 280 x 2
Shipping lbs 302 x 2 302 x 2 302 x 2
Sound Pressure
4
dB(A) 54/60 57/57 59/58
Water Temperature Range
Cooling ˚F 23 - 113 23 - 113 23 - 113
Heating ˚F 14 - 113 14 - 113 14 - 113
Synchronous Operation ˚F 23 - 113 23 - 113 23 - 113
Compressor (DC Scroll)
Type DC Scroll DC Scroll DC Scroll
Oil Type PVE/FVC68D PVE/FVC68D PVE/FVC68D
Quantity 2 2 2
Heat Exhanger
Type Stainless Steel Plate Stainless Steel Plate Stainless Steel Plate
Flow Rate Nominal GPM 20.3 + 30.4 20.3 + 35.5 35.5 + 35.5
Pressure Drop ft wg 3.7 + 6.9 3.7 + 9.2 9.2 + 9.2
Piping
Liquid Line in 3/8 + 1/2 3/8 + 1/2 1/2 + 1/2
L/P Vapor Line in 7/8 + 1-1/8 7/8 + 1-1/8 1-1/8 + 1-1/8
H/P Vapor Line in 3/4 + 3/4 3/4 + 3/4
3/4 + 3/4
Refrigerant
Type R410A R410A R410A
Charge lbs 12.8 + 12.8 12.8 + 12.8 12.8 + 12.8
Control EEV EEV EEV
Maximum Number of Indoor Units
3
32 35 45
MULTI V WATER IV HEAT RECOVERY
ARWB***BAS4
MULTI V WATER IV
Specifications Unit ARWB360BAS4 ARWB432BAS4
Frames
ARWB072BAS4
ARWB144BAS4
ARWB144BAS4
ARWB144BAS4
ARWB144BAS4
ARWB144BAS4
Tons 30 36
Nominal Capacity
Cooling
1
Btu/h 360,000 432,000
Heating
1
Btu/h 405,000 486,000
Rated Capacity
Cooling
2
Btu/h 342,000 410,000
Heating
2
Btu/h 386,000 460,000
Power Voltage V / Hz / ø 208-230/60/3 208-230/60/3
Power/Communication Wiring No x AWG 2 x 18 2 x 18
Dimensions (W×D×H) Body in 97-1/4x39-1/4x19-3/4 97-1/4x39-1/4x19-3/4
Weight
Net lbs 280 x 3 280 x 3
Shipping lbs 302 x 3 302 x 3
Sound Pressure
4
dB(A) 56/57 58/62
Water Temperature Range
Cooling ˚F 23 - 113 23 - 113
Heating ˚F 14 - 113 14 - 113
Synchronous Operation ˚F 23 - 113 23 - 113
Compressor (DC Scroll)
Type DC Scroll DC Scroll
Oil Type PVE/FVC68D PVE/FVC68D
Quantity 3 3
Heat Exhanger
Type Stainless Steel Plate Stainless Steel Plate
Flow Rate Nominal GPM 20.3 + 35.5 + 35.5 35.5 + 35.5 + 35.5
Pressure Drop ft wg 3.7 + 9.2 + 9.2 9.2 + 9.2 + 9.2
Piping
Liquid Line in 3/8 + 1/2+1/2 1/2+1/2+1/2
L/P Vapor Line in 7/8 + 1-1/8 + 1-1/8 1-1/8 +1-1/8 + 1-1/8
H/P Vapor Line in 3/4 + 3/4 + 3/4 3/4 + 3/4 + 3/4
Refrigerant
Type R410A R410A
Charge lbs 12.8 + 12.8 + 12.8 12.8 + 12.8 + 12.8
Control EEV EEV
Maximum Number of Indoor Units
3
58 64
ARWB***BAS4
MULTI V WATER IV HEAT RECOVERY
1. Nominal capacity applied with non-ducted indoor units, and is rated 0 ft. above sea level with 25 ft. of refrigerant line per indoor unit
and a 0 ft. level difference between outdoor and indoor units. All capacities are net with a Combination Ratio between 95 and 105%.
Cooling: Indoor 80°F DB, 67°F WB; Outdoor 95°F DB, 75°F WB
Heating: Outdoor 70°F DB, 59°F WB; Outdoor 47°F DB, 43°F WB
2. Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
3. The System Combination Ratio must be between 50 and 130%.
4. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
5. Due to our commitment to continued innovation, some specications may be changed without notification.