LG VRF Systems

23 24
LG Air Conditioning Technologies
MULTI V S
Specifications Unit ARUN024GSS4 ARUN038GSS4 ARUN048GSS4 ARUN053GSS4 ARUB060GSS4
Tons 2 3 4 4.4 5
Nominal Capacity
Cooling
1
Btu/h 24,000 39,500 50,000 55,500 60,000
Heating
1
Btu/h 27,000 44,000 56,500 61,500 64,000
Rated Capacity
Cooling
2
Btu/h 24,000 38,000 48,000 53,000 60,000
Heating
2
Btu/h 27,000 42,000 54,500 59,000 64,000
Power Voltage V / Hz / ø 208-230/60/1 208-230/60/1 208-230/60/1 208-230/60/1 208-230/60/1
Power/Communication Wiring No x AWG 2 x 18 2 x 18 2 x 18 2 x 18 2 x 18
Operating Range
Cooling ˚F 23 - 122 23 - 122 23 - 122 23 - 122 23 - 122
Heating ˚F -4 - 61 -4 - 61 -4 - 61 -4 - 61 -13 - 61
Dimensions (W×D×H) Body in 37-13/32 x 32-27/32 x 13 37-13/32 x 32-27/32 x 13 37-13/32 x 32-27/32 x 13 37-13/32 x 32-27/32 x 13 37-13/32 x 32-27/32 x 13
Weight
Net lbs 159 207 207 207 256
Shipping lbs 176 218 218 218 284
Sound Pressure
4
dB(A) 50 50 51 52 57
Fan (Axial Flow Fan) CFM 2,119 3,885 3,885 3,885 3,885
Compressor
Type DC Inverter DC Inverter DC Inverter DC Inverter DC Inverter
Oil Type PVE/FVC68D PVE/FVC68D PVE/FVC68D PVE/FVC68D PVE/FVC68D
Quantity 1 1 1 1 1
Heat Exhanger
Coating Gold Fin / Hydrophillic Gold Fin / Hydrophillic Gold Fin / Hydrophillic Gold Fin / Hydrophillic Gold Fin / Hydrophillic
Rows/Fins per Inch 2/14 2/14 2/14 2/14 3/14
Piping
Liquid Line in 3/8 3/8 3/8 3/8 3/8
H/P Vapor Line in - - - - 5/8
L/P Vapor Line in 5/8 5/8 5/8 3/4 3/4
Refrigerant
Type R410A R410A R410A R410A R410A
Charge lbs 4.0 6.6 6.6 6.6 8.8
Control EEV EEV EEV EEV EEV
Maximum Number of Indoor Units
3
4 6 8 9 12
1. Nominal capacity applied with non-ducted indoor units, and is rated 0 ft. above sea level with 25 ft. of refrigerant line per indoor unit
and a 0 ft. level difference between outdoor and indoor units. All capacities are net with a Combination Ratio between 95 and 105%.
Cooling: Indoor 80°F DB, 67°F WB; Outdoor 95°F DB, 75°F WB
Heating: Outdoor 70°F DB, 59°F WB; Outdoor 47°F DB, 43°F WB
2. Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
3. The System Combination Ratio must be between 50 and 130%.
4. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
5. Due to our commitment to continued innovation, some specications may be changed without notification.
1. Nominal capacity applied with non-ducted indoor units, and is rated 0 ft. above sea level with 25 ft. of refrigerant line per indoor unit
and a 0 ft. level difference between outdoor and indoor units. All capacities are net with a Combination Ratio between 95 and 105%.
Cooling: Indoor 80°F DB, 67°F WB; Outdoor 95°F DB, 75°F WB
Heating: Outdoor 70°F DB, 59°F WB; Outdoor 47°F DB, 43°F WB
2. Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
3. The System Combination Ratio must be between 50 and 130%.
4. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
5. Due to our commitment to continued innovation, some specications may be changed without notification.
ARU*****GSS4
MULTI V S
MULTI V SPACE II
Specifications Unit ARUN053GF2
Tons 4.4
Nominal Capacity
Cooling
1
Btu/h 53,000
Heating
1
Btu/h 59,000
Rated Capacity
Cooling
2
Btu/h 54,000
Heating
2
Btu/h 60,000
Power Voltage V / Hz / ø 208-230/60/1
Power/Communication Wiring No x AWG 2 x 18
Operating Range
Cooling ˚F 23 - 118
Heating ˚F -4 - +60
Dimensions (W×D×H) Body in 29-1/2 x 70-1/2 x 25-1/2
Weight
Net lbs 320
Shipping lbs 346
Sound Pressure
4
dB(A) 68.3 / 52.7
Fan (Propeller) CFM 3,532
Compressor (DC Inverter)
Oil Type PVE/FVC68D
Quantity 1
Heat Exhanger
Coating Gold Fin
Rows/Fins per Inch 2/14
Piping
Liquid Line in 3/8
Vapor Line in 3/4
Refrigerant
Type R410A
Charge lbs 7.7
Control EEV
Maximum Number of Indoor Units
3
9
ARUN053GF2
MULTI V SPACE II