LG VRF Systems

19 20
LG Air Conditioning Technologies
Specifications Unit ARUM168DTE5 ARUM192DTE5 ARUM216DTE5 ARUM241DTE5
Frames ARUM168DTE5 ARUM192DTE5 ARUM216DTE5 ARUM241DTE5
Tons 14 16 18 20
Nominal Capacity
Cooling
1
Btu/h 168,000 192,000 216,000 240,000
Heating
1
Btu/h 160,000 184,000 206,000 222,000
Rated Capacity
Cooling
2
Btu/h 189,000 216,000 243,000 243,000
Heating
2
Btu/h 180,000 206,000 230,000 230,000
Power Voltage V / Hz / ø 460/60/3 460/60/3 460/60/3 460/60/3
Power/Communication Wiring No x AWG 2 x 18 2 x 18 2 x 18 2 x 18
Operating Range
Cooling ˚F 5-122 5-122 5-122 5-122
Heating ˚F -13 - 61 -13 - 61 -13 - 61 -13 - 61
Simultaneous Operation
3
˚F 14 - 81 14 - 81 14 - 81 14 - 81
Dimensions (W×D×H) Body in 48-7/8 x 66-1/2 x 30 48-7/8 x 66-1/2 x 30 48-7/8 x 66-1/2 x 30 48-7/8 x 66-1/2 x 30
Weight
Net lbs 639 659 666 666
Shipping lbs 666 688 694 694
Sound Pressure
4
dB(A) 61.0 62.0 64.0 65.0
Fan (Propeller) CFM 11,300 11,300 11,300 11,300
Compressor (DC Scroll)
Type DC Scroll DC Scroll DC Scroll DC Scroll
Oil Type PVE/FVC68D PVE/FVC68D PVE/FVC68D PVE/FVC68D
Quantity 2 2 2 2
Heat Exhanger
Coating Black Coated Fin™ Black Coated Fin™ Black Coated Fin™ Black Coated Fin™
Rows/Fins per Inch
3/17 3/17 3/17 3/17
Piping
Liquid Line in 5/8 5/8 5/8 5/8
L/P Vapor Line in 1-1/8 1-1/8 1-1/8 1-3/8
H/P Vapor Line
5
in 7/8 1-1/8 1-1/8 1-1/8
Refrigerant
Type R410A R410A R410A R410A
Charge lbs 26.5 30.9 37.5 37.5
Control EEV EEV EEV EEV
Maximum Number of Indoor Units
6
29 32 35 39
ARUM***DTE5
MULTI V 5 MULTI V 5
MULTI V 5
ARUM***DTE5
Specifications Unit ARUM264DTE5 ARUM288DTE5 ARUM312DTE5 ARUM336DTE5
Frames
ARUM096DTE5
ARUM168DTE5
ARUM096DTE5
ARUM192DTE5
ARUM096DTE5
ARUM216DTE5
ARUM121DTE5
ARUM216DTE5
Tons 22 24 26 28
Nominal Capacity
Cooling
1
Btu/h 264,000 288,000 312,000 336,000
Heating
1
Btu/h 252,000 276,000 298,000 320,000
Rated Capacity
Cooling
2
Btu/h 297,000 324,000 351,000 378,000
Heating
2
Btu/h 283,000 309,000 333,000 359,000
Power Voltage V / Hz / ø 460/60/3 460/60/3 460/60/3 460/60/3
Power/Communication Wiring No x AWG 2 x 18 2 x 18 2 x 18 2 x 18
Operating Range
Cooling ˚F 5-122 5-122 5-122 5-122
Heating ˚F -13 - 61 -13 - 61 -13 - 61 -13 - 61
Simultaneous Operation
3
˚F 14 - 81 14 - 81 14 - 81 14 - 81
Dimensions (W×D×H) Body in 100-1/2 x 66-1/2 x 30 100-1/2 x 66-1/2 x 30 100-1/2 x 66-1/2 x 30 100-1/2 x 66-1/2 x 30
Weight
Net lbs 507+639 507+659 507+666 507+666
Shipping lbs 534+666 534+688 534+694 534+694
Sound Pressure
4
dB(A) 63.0 63.0 65.0 65.0
Fan (Propeller) CFM 22,600 22,600 22,600 22,600
Compressor (DC Scroll)
Type DC Scroll DC Scroll DC Scroll DC Scroll
Oil Type PVE/FVC68D PVE/FVC68D PVE/FVC68D PVE/FVC68D
Quantity 3 3 3 3
Heat Exhanger
Coating GBlack Coated Fin™
Black Coated Fin™ Black Coated Fin™ Black Coated Fin™
Rows/Fins per Inch 2/17+3/17 2/17+3/17 2/17+3/17 2/17+3/17
Piping
Liquid Line in 3/8 + 5/8 3/8 + 5/8 3/8 + 5/8 1/2 + 5/8
L/P Vapor Line in 7/8 + 1-1/8 7/8 + 1-1/8 7/8 + 1-1/8 1-1/8 + 1-1/8
H/P Vapor Line
5
in 3/4 + 7/8 3/4 + 1-1/8 3/4 + 1-1/8 3/4 + 1-1/8
Refrigerant
Type R410A R410A R410A R410A
Charge lbs 23.2+26.5 23.2+30.9 23.2+37.5 23.2+37.5
Control EEV EEV EEV EEV
Maximum Number of Indoor Units
6
42 45 52 55
1. Nominal capacity applied with non-ducted indoor units, and is rated 0 ft. above sea level with 25 ft. of refrigerant line per indoor unit and a 0 ft. level difference between outdoor and indoor units. All capacities are net with a
Combination Ratio between 95 and 105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80°F dry bulb (DB) and 67°F wet bulb (WB) and outdoor ambient conditions of 95°F dry bulb (DB) and 75°F wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70°F dry bulb (DB) and 59°F wet bulb (WB) and outdoor ambient conditions of 47°F dry bulb (DB) and 43°F wet bulb (WB).
2. Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
3. Temperatures shown are for Simultaneous operation - primarily cooling. The simultaneous operation range (primarily heating) is 14°F to 61°F.
4. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
5. Used in Heat Recovery Systems only.
6. The System Combination Ratio must be between 50 and 130%.
7. Due to our commitment to continued innovation, some specifications may be changed without notification.