LG VRF Systems
17 18
LG Air Conditioning Technologies
MULTI V 5
Specifications Unit ARUM432BTE5 ARUM456BTE5 ARUM480BTE5 ARUM504BTE5
Frames
ARUM121BTE5
ARUM121BTE5
ARUM192BTE5
ARUM121BTE5
ARUM121BTE5
ARUM216BTE5
ARUM121BTE5
ARUM144BTE5
ARUM216BTE5
ARUM121BTE5
ARUM168BTE5
ARUM216BTE5
Tons 36 38 40 42
Nominal Capacity
Cooling
1
Btu/h 432,000 456,000 480,000 504,000
Heating
1
Btu/h 412,000 434,000 458,000 480,000
Rated Capacity
Cooling
2
Btu/h 486,000 513,000 540,000 567,000
Heating
2
Btu/h 460,000 488,000 513,000 539,000
Power Voltage V / Hz / ø 208-230/60/3 208-230/60/3 208-230/60/3 208-230/60/3
Power/Communication Wiring No x AWG 2 x 18 2 x 18 2 x 18 2 x 18
Operating Range
Cooling ˚F 5-122 5-122 5-122 5-122
Heating ˚F -13 - 61 -13 - 61 -13 - 61 -13 - 61
Simultaneous Operation
3
˚F 14 - 81 14 - 81 14 - 81 14 - 81
Dimensions (W×D×H) Body in 155 x 66-1/2 x 30 152 x 66-1/2 x 30 152 x 66-1/2 x 30 152 x 66-1/2 x 30
Weight
Net lbs 507+507+659 507+507+666 507+639+666 507+639+666
Shipping lbs 507+507+688 534+534+694 534+666+694 534+666+694
Sound Pressure
4
dB(A) 66.0 66.0 67.0 67.0
Fan (Propeller) CFM 33,900 33,900 33,900 33,900
Compressor (DC Scroll)
Type DC Scroll DC Scroll DC Scroll DC Scroll
Oil Type PVE/FVC68D PVE/FVC68D PVE/FVC68D PVE/FVC68D
Quantity 4 4 5
5
Heat Exhanger
Coating Black Coated Fin™ Black Coated Fin™ Black Coated Fin™ Black Coated Fin™
Rows/Fins per Inch 2/17 x 2 + 3/17 2/17 x 2 + 3/17 2/17 + 3/17 x 2 2/17 + 3/17 x 2
Piping
Liquid Line in 1/2 + 1/2 + 5/8 1/2 + 1/2 + 5/8 1/2 + 1/2 + 5/8 1/2 + 1/2 + 5/8
L/P Vapor Line in 1-1/8 + 1-1/8+ 1-1/8 1-1/8 + 1-1/8+ 1-1/8 1-1/8 + 1-1/8+ 1-1/8 1-1/8 + 1-1/8+ 1-1/8
H/P Vapor Line
5
in 3/4 + 3/4 + 1-1/8 3/4 + 3/4 + 1-1/8 3/4 + 7/8 + 1-1/8 3/4 + 7/8 + 1-1/8
Refrigerant
Type R410A R410A R410A R410A
Charge lbs 23.2+23.2+30.9 23.2+23.2+37.5 23.2+26.5+37.5 23.2+26.5+37.5
Control EEV EEV EEV EEV
Maximum Number of Indoor Units
6
64 64 64 64
ARUM***BTE5
Specifications Unit ARUM072DTE5 ARUM096DTE5 ARUM121DTE5 ARUM144DTE5
Frames ARUM072DTE5 ARUM096DTE5 ARUM121DTE5 ARUM144DTE5
Tons 6 8 10 12
Nominal Capacity
Cooling
1
Btu/h 72,000 96,000 120,000 144,000
Heating
1
Btu/h 69,000 92,000 114,000 138,000
Rated Capacity
Cooling
2
Btu/h 81,000 108,000 135,000 162,000
Heating
2
Btu/h 77,000 103,000 129,000 154,000
Power Voltage V / Hz / ø 460/60/3 460/60/3 460/60/3 460/60/3
Power/Communication Wiring No x AWG 2 x 18 2 x 18 2 x 18 2 x 18
Operating Range
Cooling ˚F 5-122 5-122 5-122 5-122
Heating ˚F -13 - 61 -13 - 61 -13 - 61 -13 - 61
Simultaneous Operation
3
˚F 14 - 81 14 - 81 14 - 81 14 - 81
Dimensions (W×D×H) Body in 36-3/4 x 66-1/2 x 30 48-7/8 x 66-1/2 x 30 48-7/8 x 66-1/2 x 30 48-7/8 x 66-1/2 x 30
Weight
Net lbs 430 507 507 639
Shipping lbs 452 534 534 666
Sound Pressure
4
dB(A) 58.0 58.0 59.0 60.0
Fan (Propeller) CFM 8,470 11,300 11,300 11,300
Compressor (DC Scroll)
Type DC Scroll DC Scroll DC Scroll DC Scroll
Oil Type PVE/FVC68D PVE/FVC68D PVE/FVC68D PVE/FVC68D
Quantity 1 1 1 2
Heat Exhanger
Coating Black Coated Fin™ Black Coated Fin™ GBlack Coated Fin™ Black Coated Fin™
Rows/Fins per Inch
2/17 2/17 2/17 3/17
Piping
Liquid Line in 3/8 3/8 1/2 1/2
L/P Vapor Line in 3/4 7/8 1-1/8 1-1/8
H/P Vapor Line
5
in 5/8 3/4 3/4 7/8
Refrigerant
Type R410A R410A R410A R410A
Charge lbs 14.3 23.2 23.2 26.5
Control EEV EEV EEV EEV
Maximum Number of Indoor Units
6
13 16 20 24
ARUM***DTE5
MULTI V 5MULTI V 5
ARUM072DTE5
1. Nominal capacity applied with non-ducted indoor units, and is rated 0 ft. above sea level with 25 ft. of refrigerant line per indoor unit and a 0 ft. level difference between outdoor and indoor units. All capacities are net with a
Combination Ratio between 95 and 105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80°F dry bulb (DB) and 67°F wet bulb (WB) and outdoor ambient conditions of 95°F dry bulb (DB) and 75°F wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70°F dry bulb (DB) and 59°F wet bulb (WB) and outdoor ambient conditions of 47°F dry bulb (DB) and 43°F wet bulb (WB).
2. Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
3. Temperatures shown are for Simultaneous operation - primarily cooling. The simultaneous operation range (primarily heating) is 14°F to 61°F.
4. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
5. Used in Heat Recovery Systems only.
6. The System Combination Ratio must be between 50 and 130%.
7. Due to our commitment to continued innovation, some specifications may be changed without notification.