Submittal
MultiSITE™ CRC1 - PREMTBVC0
MultiSITE CRC1+ - PREMTBVC1
MultiSITE Comm. Mgr. - PBACNBTR0A
PI-485 - PMNFP14A1
Dry Contact - PDRYCB320
Wi-Fi Module - PWFMDD200
Low Ambient Wind Baffle (Cooling
operation to -4°F) - ZLABGP04A
Simple Controller with Mode
(White) PQRCVCL0QW
Job Name/Locaon:
Date:
PO No.:
Architect: GC:
Engr: Mech:
Rep:
(Company) (Project Manager)
For: File Resubmit
Approval Other
Tag #:
For a complete list of available accessories, contact your LG representave.
For connual product development, LG reserves the right to change specicaons without noce.
© LG Electronics U.S.A., Inc., Englewood Clis, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com
1. Acceptable operang voltage: 187V-253V.
2. Piping lengths are equivalent.
3. Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745.
4. All communication / connection (power) cable from the outdoor unit to the indoor unit
is field supplied and is to be minimum four-conductor, 18 AWG, stranded, shielded or un-
shielded (if shielded, it must be grounded to the chassis of the outdoor unit only), and must
comply with applicable local and national codes.
5. See Engineering Manual for sensible and latent capacies.
6. Power wiring cable size must comply with the applicable local and naonal code.
7. The indoor unit comes with a dry helium charge.
8. This data is rated 0 . above sea level, with 24.6 . of refrigerant line and a 0 . level dier-
ence between outdoor and indoor units.
9. Must follow installaon instrucons in the applicable LG installaon manual.
10. Mul compable 18k IDUs include socket adapters for refrigerant pipe connecons with
Single Zone systems.
Notes:
Performance:
Cooling:
Cooling (Min~Rated~Max, Btu/h)
SEER
EER
Heang:
Heang Nominal Test Condions:
Indoor: 70°F DB / 60°F WB
Outdoor: 47°F DB / 43°F WB
Heating (Min~Rated~Max, Btu/h)
HSPF
Max. Heating @ Indoor 70°F DB (Btu/h)
Outdoor 17°F WB
Outdoor 5°F WB
Outdoor -4°F WB
Outdoor -13°F WB
SEER - Seasonal Energy Eciency Rao EER - Energy Eciency Rao
Power Supply
1
(V/Hz/Ø)
208-230/60/1
HSPF - Heang Seasonal Performance Factor
Cooling Nominal Test Condions:
Indoor: 80°F DB / 67°F WB
Outdoor: 95°F DB / 75°F WB
Electrical:
MOP (A)
MCA (A)
Cooling / Heating Rated Amps (A)
Compressor (A)
Fan Motor (IDU + ODU) (A)
Locked Rotor Amps (A)
MCA - Minimum Circuit Ampacity
MOP - Maximum Overcurrent Protection
Cooling Power Input (Min~Rated~Max, kW)
Heating Power Input (Min~Rated~Max, kW)
Piping:
Installed Liquid Pipe (in., O.D.)
Installed Vapor Pipe (in., O.D.)
IDU Liquid Connection (in., O.D.)
IDU Vapor Connection (in., O.D.)
Addional Refrigerant (oz./.)
Min. / Max. Pipe Length² (.)
Piping Length (no add’l refrig., .)
Max. Elevaon (.)
3/8
5/8
Features:
• ESP control
• Hot start
• Condensate Pump
• Inverter (variable speed)
• ODU drain pan heater
• IDU compatible with
Multi F ODUs
• Smart Diagnosis
• Optional Wi-Fi control
• Auto restart
• Control lock
• Group control
• Timer (on/o)
• Sleep Mode
Oponal Accessories:
Cooling (°F DB)
Heang (°F WB)
5 ~ 118
-13 ~ 64
Operang Range:
Outdoor Unit:
Indoor Unit:
Cooling (°F WB)
Heang (°F DB)
57 ~ 77
59 ~ 81
System Data:
Fan:
ODU Type
IDU Type
Fan Speeds (Fan/Cool/Heat)
Fan Quantity (ODU + IDU)
Motor/Drive
Maximum ODU Air Volume (CFM)
IDU Air Volume H/M/L (CFM)
Dehumidification (pts./hr.)
IDU External Static Pressure (ESP)
Operating Range (Min ~ Default ~
Max) (in wg)
Propeller
Sirocco
3 / 3 / 3
1 + 3
Brushless Digitally Controlled/Direct
Page 1 of 3
Required Accessories (sold separately):
Controller (Any LG wired remote controller)
R410A
EEV
Refrigerant Type
Refrigerant Control
Refrigerant Charge (lbs.)
ODU Sound Pressure
3
(Cooling / Heating) ±1 dB(A)
IDU Sound Pressure
3
(Cooling / Heating) ±1 dB(A)
ODU Net / Shipping Weight (lbs.)
IDU Net / Shipping Weight (lbs.)
Heat Exchanger Coating
GoldFin™
98.4
6,800 ~ 20,000 ~ 24,000
1/2
22,550
12.5
0.51 ~ 1.44 ~ 2.00
23
48.5 / 57.3
530 / 441 / 353
4.4
6.4 / 8.1
51 / 52
133.4 / 144.4
15,990
2.2
16.4 / 164
36 / 34 / 31
LD187HHV4
22
10
30
24.9
17,970
18.8
2,048
Single Zone Low Static Ducted with LGRed°
3.84
0.43
Outdoor Unit (ODU) - LUU180HHV, Indoor Unit (IDU) - LDN187HV4
7,200 ~ 18,000 ~ 22,000
0.47 ~ 1.82 ~ 2.50
14.5
20,000
1/4
SB_SZ_Low_Static_Ducted_LD187HHV4_2020_09_25_142203
0.0 ~ 0.1 ~ 0.2