Install Instructions

46
Single Zone High Efciency, Standard, Extended Pipe and Mega Wall Mount Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
ELECTRICAL WIRING
Additional screens can be accessed by tabs on the main screen.
Additional screens include the following:
1. Cycleview (Figure 67): Graphic of internal components including:
•Compressors showing actual speeds
•EEVs
•IDUs
•Temperature and pressure sensors
•Four-way reversing valve
2. Graph: Full screen graph of actual high and low pressures and high
and low pressure limits. A sliding bar enables user to go back in
time and view data.
3. Control FTN: Enables user to turn on IDUs in 1.8°F increments.
4. Useful Tab
•Unit Conversion: Converts metric values to imperial values.
•Actual inverter compressor speed
•Target inverter compressor speed
•Actual outdoor fan speed
•Target outdoor unit fan speed
•Actual superheat
•Target superheat
•Actual subcooler circuit superheat
•Target subcooler circuit superheat
•Main EEV position
•Subcooling EEV position
•Inverter compressor current transducer value
•Outdoor air temperature
•Actual high pressure/saturation temperature
•Actual low pressure/saturation temperature
•Suction temperature
•Inverter compressor discharge temperature
•Front outdoor coil pipe temperature
•Back outdoor coil pipe temperature
•Liquid line pipe temperature
•Subcooler inlet temperature
•Subcooler outlet temperature
•Average indoor unit (IDU) pipe temperature
•Inverter compressor operation indicator light
•Liquid injection
valves’ operation
indicator lights
•Hot gas bypass valve
operation indicator
light
•Four-way reversing
valve operation
indicator light
•Pressure graph
showing actual low
pressure and high
pressure levels
•Error code display
•Operating mode
indicator
•Target high pressure
•Target low pressure
•PCB (printed circuit board) version
•Software version
•Installer name
•Model number of IDUs
•Site name
•Total number of connected IDUs
•Communication indicators
•IDU capacity
•IDU operating mode
•IDU fan speed
•IDU EEV position
•IDU room temperature
•IDU inlet pipe temperature
•IDU outlet pipe temperature
•IDU error code
LG Monitoring View (LGMV) Diagnostic Software
LGMV software (PRCTSL1 and PRCTFE1) allows the service technician or commissioning agent to connect a computer USB port to the
Single Zone unit’s main printed circuit board (PCB) using an accessory cable without the need for a separate interface device. The monitor-
ing screen for LGMV allows the user to view the following real time data on one screen (Figure 66):
Figure 66: MV Real-time Data Screen
Figure 67: MV Cycleview
Images on these pages are examples of LGMV screenshots. Actual images may differ depending on the version of the software and the unit installed.
Self Diagnosis Functions