GENERAL INSTALLATION GUIDELINES
Piping Support / Piping Sleeves
Figure 26: Typical Pipe Support Location—
Change in Pipe Direction
Pipe Supports, continued.
A properly installed pipe system will have sufficient supports to avoid pipes from sagging
during the life of the system. As necessary, place supports closer for segments where
potential sagging could occur. Maximum spacing of pipe supports shall meet local codes.
If local codes do not specify pipe support spacing, pipe shall be supported:
•Maximumoffivefeet(5′)oncenterforstraightsegmentsofpipeupto3/4"outside
diameter size.
•Maximumofsixfeet(6′)oncenterforpipeuptooneinch(1″)outsidediametersize.
•Maximumofeightfeet(8′)oncenterforpipeuptotwoinches(2″)outsidediametersize.
Wherever the pipe changes direction, place pipe clamps within twelve (12) inches on
one side and within twelve to nineteen (12 to 19) inches of the bend on the other side as
shown in Figure 26.
A
B
Pipe
Clamps
A + B ≈ 12”–19”
Pipe Sleeves at Penetrations
LG requires that all pipe penetrations through walls, floors, and pipes buried underground be properly insulated and routed through an
appropriate wall sleeve of sufficient size to prevent compression of refrigerant pipe insulation and free movement of the pipe within the sleeve
(Figure 27). Underground refrigerant pipe shall be routed inside a protective sleeve to prevent insulation deterioration. Refer to Figure 26.
Figure 27: Pipe Sleeve Options.
Diameterofpenetrationsshallbedeterminedbypipediameterplusthethicknessoftheinsulation.