Engineering Bulletin

Due to our policy of continuous product innovation, some specications may change without notication.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
44 | MULTI F OUTDOOR UNIT
Multi F and Multi F MAX Heat Pump System Engineering Manual
MULTI
F
MAX
MULTI
F
Table 37: LMU18CHV Cooling Capacity Table — Ducted (continued) and Mixed Indoor Units.
Connected Indoor
Units
Combination
Capacity
Index
Outdoor Air
Temp. (°F
DB)
Indoor Air Temp. °F DB / °F WB
68 / 57 73 / 61 77 / 64 80 / 67 86 / 72 90 / 75
TC PI TC PI TC PI TC PI TC PI TC PI
Two (2)
Ducted Indoor
Units
12 + 12
14 13.72 0.82 14.58 0.85 15.43 0.88 16.04 0.89 17.13 0.91 17.99 0.92
20 13.71 0.83 14.57 0.86 15.42 0.89 16.03 0.90 17.12 0.92 17.97 0.94
25 13.70 0.84 14.55 0.87 15.41 0.90 16.02 0.92 17.11 0.93 17.96 0.95
30 13.69 0.85 14.54 0.89 15.39 0.92 16.01 0.93 17.09 0.95 17.94 0.96
35 13.68 0.87 14.53 0.90 15.38 0.93 16.00 0.94 17.08 0.96 17.93 0.98
40 13.67 0.88 14.52 0.91 15.37 0.94 15.98 0.95 17.07 0.97 17.92 0.99
45 13.66 0.89 14.51 0.92 15.36 0.96 15.97 0.97 17.06 0.98 17.90 1.00
50 13.65 0.90 14.50 0.93 15.35 0.97 15.96 0.98 17.04 1.00 17.89 1.02
55 13.64 0.91 14.49 0.95 15.33 0.98 15.95 0.99 17.03 1.01 17.88 1.03
60 13.63 0.92 14.48 0.96 15.32 0.99 15.93 1.00 17.02 1.02 17.86 1.04
65 13.62 0.94 14.47 0.97 15.31 1.01 15.92 1.02 17.00 1.04 17.85 1.06
70 13.61 0.95 14.45 0.98 15.30 1.02 15.91 1.03 16.99 1.05 17.83 1.07
75 13.28 1.00 14.12 1.04 14.97 1.07 15.58 1.09 16.65 1.11 17.50 1.13
80 12.95 1.05 13.80 1.09 14.64 1.13 15.24 1.14 16.32 1.16 17.16 1.19
85 12.63 1.10 13.47 1.14 14.31 1.18 14.91 1.20 15.99 1.22 16.82 1.24
90 12.30 1.15 13.14 1.19 13.98 1.24 14.58 1.25 15.65 1.28 16.49 1.30
95 11.95 1.20 12.79 1.25 13.62 1.29 14.00 1.31 15.28 1.33 16.12 1.36
100 11.66 1.25 12.49 1.30 13.33 1.35 13.82 1.36 14.99 1.39 15.82 1.42
105 11.37 1.31 12.20 1.35 13.04 1.40 13.64 1.42 14.70 1.45 15.53 1.47
110 11.08 1.36 11.91 1.41 12.74 1.46 13.35 1.47 14.41 1.50 15.24 1.53
115 10.79 1.41 11.62 1.46 12.45 1.51 13.06 1.53 14.12 1.56 14.95 1.59
118 10.61 1.44 11.45 1.49 12.28 1.55 12.88 1.56 13.94 1.59 14.78 1.62
122 10.56 1.48 11.39 1.53 12.22 1.59 12.82 1.61 13.89 1.64 14.72 1.67
Two (2) Mixed
Indoor Units
7 + 9
14 14.30 0.78 15.19 0.80 16.08 0.83 16.72 0.84 17.85 0.86 18.74 0.88
20 14.29 0.79 15.18 0.82 16.06 0.85 16.71 0.85 17.84 0.87 18.73 0.89
25 14.28 0.80 15.17 0.83 16.05 0.86 16.69 0.87 17.83 0.88 18.71 0.90
30 14.27 0.81 15.15 0.84 16.04 0.87 16.68 0.88 17.81 0.90 18.70 0.91
35 14.26 0.82 15.14 0.85 16.03 0.88 16.67 0.89 17.80 0.91 18.68 0.93
40 14.25 0.83 15.13 0.86 16.02 0.89 16.65 0.90 17.79 0.92 18.67 0.94
45 14.24 0.84 15.12 0.87 16.00 0.90 16.64 0.92 17.77 0.93 18.66 0.95
50 14.22 0.85 15.11 0.88 15.99 0.92 16.63 0.93 17.76 0.94 18.64 0.96
55 14.21 0.86 15.10 0.90 15.98 0.93 16.62 0.94 17.74 0.96 18.63 0.98
60 14.20 0.88 15.08 0.91 15.97 0.94 16.60 0.95 17.73 0.97 18.61 0.99
65 14.19 0.89 15.07 0.92 15.95 0.95 16.59 0.96 17.72 0.98 18.60 1.00
70 14.18 0.90 15.06 0.93 15.94 0.96 16.58 0.98 17.70 0.99 18.58 1.01
75 13.84 0.95 14.72 0.98 15.60 1.02 16.23 1.03 17.35 1.05 18.23 1.07
80 13.50 0.99 14.37 1.03 15.25 1.07 15.88 1.08 17.00 1.10 17.88 1.12
85 13.16 1.04 14.03 1.08 14.91 1.12 15.54 1.13 16.66 1.15 17.53 1.18
90 12.82 1.09 13.69 1.13 14.57 1.17 15.20 1.19 16.31 1.21 17.18 1.23
95 12.45 1.14 13.32 1.18 14.19 1.22 14.59 1.24 15.93 1.26 16.79 1.29
100 12.15 1.19 13.02 1.23 13.89 1.28 14.40 1.29 15.62 1.32 16.49 1.34
105 11.85 1.24 12.72 1.28 13.58 1.33 14.21 1.34 15.32 1.37 16.19 1.40
110 11.54 1.29 12.41 1.33 13.28 1.38 13.91 1.40 15.02 1.42 15.88 1.45
115 11.24 1.33 12.11 1.38 12.98 1.43 13.60 1.45 14.71 1.48 15.58 1.51
118 11.06 1.36 11.93 1.41 12.80 1.46 13.42 1.48 14.53 1.51 15.40 1.54
122 11.00 1.40 11.87 1.45 12.73 1.51 13.36 1.52 14.47 1.55 15.34 1.58
TC = Total Capacity (kBtu/h).
PI = Power Input (kW).
Nominal capacity as rated: 0 ft. above sea level with 25 ft. of refrigerant piping.
0 ft. level difference between outdoor and indoor units.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and
67ºF wet bulb (WB), and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
The shaded table rows indicate reference data. When operating at this temperature, these values can
be different if the system is not running consistently.
PERFORMANCE DATA
Cooling Capacity Tables