SINGLE ZONE MEGA, STANDARD EFFICIENCY, AND MEGA 115V WALL MOUNTED ENGINEERING MANUAL 3/4, 1, 1-1/2, and 2 Tons Mega, Standard Efficiency Models: LS090HEV2, LS090HFV3 LS120HEV2, LS120HFV3 LS180HEV2, LS180HFV3 LS240HEV2, LS240HFV3 3/4 and 1 Tons Mega 115V Models: LS090HXV2 LS120HXV2
PROPRIETARY DATA NOTICE This document, as well as all reports, illustrations, data, information, and other materials are the property of LG Electronics U.S.A., Inc., and are disclosed by LG Electronics U.S.A., Inc. only in confidence. This document is for design purposes only. A summary list of safety precautions is on page 3 For more technical materials such as submittals, catalogs, installation, owner’s, and service manuals, visit www.lghvac.com. For continual product development, LG Electronics U.S.A.
TABLE OF CONTENTS Unit Nomenclature���������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������� 4 LG Air Conditioner Technical Solution (LATS) ��������������������������������������������������������������������������������������������������������������������������������������������������������� 5-6 Mega, Standard Efficiency, and Mega 115V Product Data 7-50 Mechanica
Single Zone Mega, Standard Efficiency, and Mega 115V Wall Mounted Engineering Manual UNIT NOMENCLATURE Single Zone Wall Mount Indoor and Outdoor Units LS N 090 HEV Family LA= Art Cool Premier / Gallery / Mirror LS= High Efficiency Wall Mount / Standard / Mega Type N = Indoor Wall Mount Unit U = Outdoor Heat Pump Unit No N or U: System Nominal Capacity (Nominal cooling capacity in Btu/h) 090 = 9,000 120 = 12,000 180 = 18,000 240 = 24,000 300/307 = 30,000 360 = 36,000 Indoor/Outdoor Product HEV = Mega H
LG AIR CONDITIONER TECHNICAL SOLUTION (LATS) LG Air Conditioner Technical Solution (LATS) Software A properly designed and installed refrigerant piping system is critical to the optimal performance of LG air-conditioning systems. To assist engineers, LG offers, free of charge, LG Air Conditioner Technical Solution (LATS) software—a total design solution for LG air conditioning systems. Contact your LG Rep for the best software program for your application.
Single Zone Mega, Standard Efficiency, and Mega 115V Wall Mounted Engineering Manual LG AIR CONDITIONER TECHNICAL SOLUTION (LATS) LATS Generates a Complete Project Report LATS software also generates a report containing project design parameters, cooling and heating design data, system component performance, and capacity data.
PRODUCT DATA Mechanical Specifications on page 8 General Data on page 9 Electrical Data on page 13 Functions, Controls, Options on page 14 Outdoor Unit Dimensions on page 15 Indoor Unit Dimensions on page 18 Acoustic Data on page 20 Refrigerant Flow Diagrams on page 26 Indoor Unit Wiring Diagrams on page 28 Outdoor Unit Wiring Diagrams on page 30 Electrical Connections on page 33 Air Flow, Static Pressure, and Temperature Distribution on page 37 Accessories on page 49
MECHANICAL SPECIFICATIONS Single Zone Mega, Standard Efficiency, and Mega 115V Wall Mounted Engineering Manual Single Zone Mega, Standard Efficiency, and Mega 115V General LG Single Zone Mega, Standard Efficiency, and Mega 115V Wall Mounted systems comprise of a single outdoor unit connected to a single indoor unit with a single refrigerant circuit. This system is a Duct-Free Split system that can operate in either cooling or heating mode.
GENERAL DATA Pairing Table The following table shows the available outdoor and indoor unit, along with the factory provided controller.
GENERAL DATA Single Zone Mega, Standard Efficiency, and Mega 115V Wall Mounted Engineering Manual Specifications Table 2: Single Zone Mega System Specifications. System Model Number (IDU/ODU) LS090HEV2 (LSN090HEV2/ LSU090HEV2) LS120HEV2 (LSN120HEV2/ LSU120HEV2) LS180HEV2 (LSN180HEV2/ LSU180HEV2) LS240HEV2 (LSN240HEV2/ LSU240HEV2) 3,070 ~ 9,000 ~10,330 3,070 ~ 12,000 ~ 13,780 3,685 ~ 18,000 ~ 18,493 3,685 ~ 22,000 ~ 24,000 Cooling Capacity (Min/Rated/Max) (Btu/h) 0.72 1.142 1.5 2.
GENERAL DATA Specifications EEV: Electronic Expansion Valve IDU: Indoor Unit ODU: Outdoor Unit This unit comes with a dry helium charge. This data is rated 0 ft above sea level with 24.6 of refrigerant line per indoor unit and a 0 ft level difference outdoor and indoor units. Cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
GENERAL DATA Single Zone Mega, Standard Efficiency, and Mega 115V Wall Mounted Engineering Manual Specifications Table 4: Single Zone Mega 115V System Specifications.
ELECTRICAL DATA Mega, Standard Efficiency, and Mega 115V Outdoor Units Electrical Data for Mega, Standard Efficiency Models Table 5: 208-230V, 60Hz, 1-Phase Single Zone Mega, Standard Efficiency System Electrical Data Table. Nominal Unit Model Hertz Voltage Voltage Range MCA Tons No. (Min. to Max.) MOP Compressor Quantity Compressor Motor Outdoor Fan Motor Indoor Fan Motor RLA Cooling Heating W FLA W FLA 3/4 LS090HEV2 10.0 15 1 7.0 7.0 43 0.4 30 0.4 1 LS120HEV2 10.0 15 1 7.0 7.
Table 7: Indoor Units—Functions, Controls and Options.
OUTDOOR UNIT DIMENSIONS LSU090HFV3, LSU120HFV3, LSU090HEV2, LSU120HEV2, LSU090HXV2, Power and Communication Cable Access Hole Service Valve Cover 2-7/32 (56) LSU120HXV2 14-5/8 (371) 5-3/32 (129) Product Data Liquid Pipe Connection (Flare) Air Outlet Ø16-1/4 (413) Control Box Vapor Pipe Connection (Flare) 5/8 (16) 2-9/16 (65) 28-7/32 (717) 10-1/2 (267) 18-7/32 (463) 3-1/2 (89) 3/16 (5) 9-1/4 (235) 9-27/32 (250) 10-5/8 (270) Drain Hole 2-Ø13/16 (20) 19-1/2 (495) 9/16 (14) Unit: Inch (mm) 21
12-11/16 (322) 5-5/8 (143) 1-1/32 (26) 12-5/16 (313) PRODUCT DATA Air Outlet 34-1/4 (870) 23-1/16 (586) 20-9/32 (515) Drain Hole 2-Ø13/16 (20) 15-3/16 (386) 1-1/4 (32) Due to our policy of continuous product innovation, some specifications may change without notification. © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG ” is a registered trademark of LG Corp.
OUTDOOR UNIT CORNER WEIGHT AND CENTER OF GRAVITY DIMENSIONS Figure 3: Mega, Standard Efficiency, and Mega 115V Outdoor Unit Corner Weight and Center of Gravity Dimensions. d A D e c C B b Product Data a Table 8: Mega, Standard Efficiency, and Mega 115V Outdoor Unit Corner Weight and Center of Gravity Dimensions. Model No. Weight (lb.) Shipping Center of Gravity (Inch) Net a b Leg (Inch) c d e Corner Weight (lb.
2-7/32 (56) 5-31/32 (152) 1/8(3) x 1/4(6) 1/4(6) x 1/8(3) 2-7/16 (61.5) 1-1/4 (31) 1-3/32 (50.2) 1-1/16 (26.2) 2 (51) 2 1-9/32(32.7) Knock-Out Refrigerant, Drain Pipe and Cable Routing Hole 2-13/32(61) 1-7/16(33.5) Decoration Cover 28-5/32 (715) Air Outlet Hole 32-15/16 (837) Due to our policy of continuous product innovation, some specifications may change without notification. © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved.
1/8(3) x 1/4(6) 1/4(6) x 1/8(3) 2-7/16 (61.5) 1-1/4 (31) 1-3/32 (50.2) 1-1/16 (26.2) 2-3/8 (60) 2-13/32(61) 2-3/8 (60) Knock-Out Refrigerant, Drain Pipe and Cable Routing Hole 5-31/32 (152) [6-11/16 (170)] Air Intake Hole 1-7/16(33.5) [2 Air -29/ 3 O utle 2 (7 t H 4)] ole 1-9/32(32.7) 5/8(15.3) Decoration Cover 34-11/32 (872) Air Outlet Hole 39-9/32 (998) Due to our policy of continuous product innovation, some specifications may change without notification. © LG Electronics U.S.A., Inc.
ACOUSTIC DATA Mega, Standard Efficiency, and Mega 115V Indoor Units Indoor Unit Sound Pressure Measurement / Sound Pressure Levels Figure 4: Indoor Unit Sound Level Measurement. • Measurements are taken 3.3 ft away from the front of the unit. • Sound pressure levels are measured in dB(A) with a tolerance of ±1. • Data is valid at nominal operation conditions. Operating conditions are assumed to be standard.
Octave Band Pressure Level (0 dB = 20 μPa) Octave Band Pressure Level (0 dB = 20 μPa) NC-65 60 NC-60 NC-55 50 NC-50 NC-45 40 NC-40 NC-35 30 NC-30 NC-25 20 Approximate Hearing Threshold NC-65 60 NC-60 NC-55 50 NC-50 NC-45 40 NC-40 ACOUSTIC DATA Mega, Standard Efficiency Indoor Units NC-35 30 NC-30 NC-25 20 Approximate Hearing Threshold NC-20 NC-20 LSN120HEV2, LSN180HEV2, LSN240HEV2 and LSN120HFV3, LSN180HFV3, LSN240HFV3 Sound Pressure Levels 10 63 NC-15 125 250 500 1000 2000 4000
ACOUSTIC DATA LSN090HXV2 and LSN120HXV2 Sound Pressure Levels Figure 9: Sound Pressure Levels for LSN090HXV2 Indoor Units.
ACOUSTIC DATA Mega, Standard Efficiency, and Mega 115V Outdoor Units Outdoor Unit Sound Pressure Measurement / Sound Pressure Levels Figure 11: Outdoor Unit Sound Levels • Measurements are taken 3.3 ft away from the front of the unit. • Sound pressure levels are measured in dB(A) with a tolerance of ±1. • Data is valid at nominal operation conditions. Operating conditions are assumed to be standard.
NC-60 NC-55 50 ACOUSTIC DATA NC-50 NC-45 40 NC-40 Octave Band Pressure Level (0 dB = 20 μPa) Octave Band Pressure Level (0 dB = 20 μPa) NC-65 60 NC-65 60 NC-60 NC-55 50 NC-50 NC-45 40 Mega, Standard Efficiency Outdoor Units NC-35 30 NC-30 NC-25 Approximate Hearing Threshold NC-35 NC-30 NC-25 20 NC-20 Approximate Hearing Threshold LSU120HEV2, LSU180HEV2, LSU240HEV2 and LSU120HFV3, LSU180HFV3, LSU240HFV3 Sound Pressure Levels 10 63 NC-15 125 250 500 1000 2000 4000 Octave Band Center F
ACOUSTIC DATA Mega 115V Outdoor Units LSU090HXV2 and LSU120HXV2 Sound Pressure Levels Figure 16: Sound Pressure Levels for LSU090HXV2 Outdoor Units.
REFRIGERANT FLOW DIAGRAMS Single Zone Mega, Standard Efficiency, and Mega 115V Wall Mounted Engineering Manual Mega, Standard Efficiency Models Refrigerant Flow Diagram for LS090 ~ 240HEV2 and LS090 ~ 240HFV3 models Indoor Unit Outdoor Unit Field Pipin g (Copper Tubing) Flare Joint Liquid Side 2-Way Valve Strainer M TH1 Heat Exchanger (Evaporator) Strainer EEV (Electronic Expansion Valve) TH2 3-Way Valve Cross Flow Fan TH3 TH4 Propeller Fan M Reversing Valve (4-Way Valve) Field Pipin g (Cop
REFRIGERANT FLOW DIAGRAMS Mega 115V Models Refrigerant Flow Diagram for LS090 ~ 120HXV2 models Indoor Unit Outdoor Unit Field Pipin g (Copper Tubing) Flare Joint Liquid Side 2-Way Valve Strainer M TH1 Heat Exchanger (Evaporator) TH4 Propeller Fan M TH2 3-Way Valve Cross Flow Fan TH3 Strainer EEV (Electronic Expansion Valve) Reversing Valve (4-Way Valve) Field Pipin g (Copper Tubing) TH5 Product Data Flare Joint Heat Exchanger (Condenser) Vapor Side TH6 Mufflers Compressor Table 13: M
INDOOR UNIT WIRING DIAGRAM CN-DISP3 CN-CC CN-LINK CN-TH3 CN-TH1 CN-DISP1 Wiring Diagram for LSN090 ~ 240HEV2 and LSN090~240HFV3 models CN-REMO CN-TH2 Single Zone Mega, Standard Efficiency, and Mega 115V Wall Mounted Engineering Manual Mega, Standard Efficiency Models THERMISTOR (AIR) THERMISTOR (MIDDLE PIPE) WATER LEVEL SENSOR WIRED REMOTE CONTROLLER DRY CONTACT MEZ64135636_Rev.
INDOOR UNIT WIRING DIAGRAM Mega 115V Models Wiring Diagram for LSN090 ~ 120HXV2 models Factory Wiring Field Wiring Option Product Data WIRED REMOTE CONTROLLER DRY CONTACT MEZ64135636 7/19 Due to our policy of continuous product innovation, some specifications may change without notification. © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG ” is a registered trademark of LG Corp.
OUTDOOR UNIT WIRING DIAGRAM Single Zone Mega, Standard Efficiency, and Mega 115V Wall Mounted Engineering Manual Mega, Standard Efficiency Models Wiring Diagram for LSU090 ~ 120HEV2 and LSU090 ~ 120HFV3 models Factory Wiring Field Wiring Option MEZ64835136 30 | PRODUCT DATA Due to our policy of continuous product innovation, some specifications may change without notification. © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG ” is a registered trademark of LG Corp.
OUTDOOR UNIT WIRING DIAGRAM Mega, Standard Efficiency Models Wiring Diagram for LSU180 ~ 240HEV2, and LSU180 ~ 240HFV3 Factory Wiring Field Wiring Option Product Data MEZ66177431 Due to our policy of continuous product innovation, some specifications may change without notification. © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG ” is a registered trademark of LG Corp.
OUTDOOR UNIT WIRING DIAGRAM Wiring Diagram for LSU090HXV2 and LSU120HXV2 Factory Wiring Field Wiring Option MVC JIG REVERSING VALVE REACTOR BK CN_LGMV CN_COIL2 CN_TH1 RD CN_TH2 CN_EEV1 250 V / T3.15 A 250 V / T20 A WCN-P(L) Connverter WCN-P(N) 250 V / T20 A RD BL YL BR U RD V BL W CN-COM SURGE ABSORBER CN2 Outdoor PWB ASSY CN3 BK BK USE COPPER CONDUCTORS ONLY | CN_COIL1 CN_COMP 250 V / T3.
ELECTRICAL CONNECTIONS General Power Wiring / Communications Cable Guidelines • • • • • • Follow manufacturer’s circuit diagrams displayed on the inside of the control box cover. Confirm power source specifications. Properly ground the outdoor unit and the indoor unit per National Electrical Code (NEC) and local codes. Connect the wiring firmly so that the wires cannot be easily pulled out. Confirm that the electrical capacity is sufficient.
Single Zone Mega, Standard Efficiency, and Mega 115V Wall Mounted Engineering Manual ELECTRICAL CONNECTIONS Figure 18: LS090HEV2, LS120HEV2, LS090HFV3, LS120HFV3 General Power / Communications System Schematic. Figure 19: Terminal Block Wiring Diagram LS090HEV2, LS120HEV2, LS090HFV3, LS120HFV3 Power Supply Circuit Breaker Indoor Unit 208/230 VAC Ground Wiring Outdoor Unit Figure 20: LS180HEV2, LS240HEV2, LS180HFV3, LS240HFV3 General Power / Communications System Schematic. .
ELECTRICAL CONNECTIONS Figure 22: LS090HXV2 and LS120HXV2 General Power / Communications System Schematic. Figure 23: Terminal Block Wiring Diagram LS090HXV2, LS120HXV2 Power Supply Circuit Breaker Indoor Unit 115 VAC Ground Wiring Outdoor Unit Controller Options Single Zone Mega, Standard Efficiency, and Mega 115V Wall Mount systems include a wireless handheld remote controller (Model No. AKB74955602). Optional LG-suppled wired controllers are available.
Figure 26: PZCWRC1 LG Wired Remote Extension Cable. Verify the connectors are properly inserted. C/BOX Cable (Plug type) To Indoor Unit CN-REMO Terminal FAN SPEED TEMP OPER MODE Extension cable Figure 27: Wired Controller Connection on the Indoor Unit Terminal Block (Appearances and Terminal Placement Will Vary Depending on Model).
AIR FLOW, STATIC PRESSURE, AND TEMPERATURE DISTRIBUTION Table 15: Mega, Standard Efficiency, and Mega 115V Outdoor Unit Air Flow Rate and Static Pressure. Model No. Mega, Standard Efficiency Air Flow Rate (CFM) Static Pressure (in. WG) LSU090 ~ 120HEV2, LSU090 ~ 120HFV3 LSU180 ~ 240HEV2, LSU180 ~ 240HFV3 953 1,730 0.0284 0.0387 LSU090HXV2, LSU120HXV2 953 0.0284 Mega 115V LSN090HEV2, LSN090HFV3 Cooling Temperature [˚C (˚F)] Air Velocity [m/s (ft./s)] 2(6.6) 0.3(1) 0.5(1.6) 1(3.
Single Zone Mega, Standard Efficiency, and Mega 115V Wall Mounted Engineering Manual AIR FLOW AND TEMPERATURE DISTRIBUTION LSN090HEV2, LSN090HFV3, continued. Heating Air Velocity [m/s (ft./s)] 0.3(1) 0.5(1.6) Temperature [ 2(6.6) 1(3.3) m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.6 0 m 2 ft. 6.6 1 3.3 0 0 ( )] m ft. 6.6 28(82) 2 26(79) 22(72) 24(75) m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.6 0 1 3.
AIR FLOW AND TEMPERATURE DISTRIBUTION LSN120HEV2, LSN120HFV3 Cooling Temperature [˚C (˚F)] Air Velocity [m/s (ft./s)] 2(6.6) 0.3(1) 0.5(1.6) 1(3.3) m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.6 0 m 2 ft. 6.6 1 3.3 0 0 m 24(75) 22(72) 2 ft. 6.6 1 3.3 0 0 26(79) 28(82) m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.6 0 Side View Discharge Angle : 35˚ (From the floor Vertical Louver : Center Fan Speed : Power ) Air Velocity [m/s (ft./s)] m ft. 5 16.4 0.3(1) m ft.
Single Zone Mega, Standard Efficiency, and Mega 115V Wall Mounted Engineering Manual AIR FLOW AND TEMPERATURE DISTRIBUTION LSN120HEV2, LSN120HFV3, continued. Heating Temperature [˚C (˚F)] Air Velocity [m/s (ft./s)] 0.3(1) 0.5(1.6) 2(6.6) 1(3.3) m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.6 0 m 2 ft. 6.6 1 3.3 0 0 22(72) 28(82) m 10 8 ft. 32.8 26.2 24(75) 26(79) 6 4 2 0 19.7 13.1 6.6 0 m 2 ft. 6.6 1 3.
AIR FLOW AND TEMPERATURE DISTRIBUTION LSN180HEV2, LSN180HFV3 Cooling Air Velocity [m/s (ft./s)] Temperature [℃ (℉)] 2(6.6) 0.3(1) 0.5(1.6) 1(3.3) m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.6 0 m 2 ft. 6.6 1 3.3 0 0 24(75) 28(82) 22(72) 20(68) 26(79) m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.6 0 m 2 ft. 6.6 1 3.3 0 0 Side View Discharge Angle : 25˚ (From the floor Vertical Louver : Center Fan Speed : Power ) Air Velocity [m/s (ft./s)] m ft. 5 16.4 0.
Single Zone Mega, Standard Efficiency, and Mega 115V Wall Mounted Engineering Manual AIR FLOW AND TEMPERATURE DISTRIBUTION LSN180HEV2, LSN180HFV3, continued. Heating Air Velocity [m/s (ft./s)] 0.3(1) 0.5(1.6) Temperature [℃ (℉)] 2(6.6) 1(3.3) 1.5(4.9) m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.6 0 m 2 ft. 6.6 1 3.3 0 0 m 24(75) 26(79) 32(90) 2 ft. 6.6 1 3.3 0 0 28(82) m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.
AIR FLOW AND TEMPERATURE DISTRIBUTION LSN240HEV2, LSN240HFV3 Cooling Temperature [˚C (˚F)] Air Velocity [m/s (ft./s)] 2(6.6) 0.3(1) 0.5(1.6) 1(3.3) 1.5(4.9) m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.6 0 m 2 ft. 6.6 1 3.3 0 0 28(82) 26(79) 24(75) 22(72) 18(64) 2 m ft. 6.6 1 3.3 0 0 m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.6 0 Side View ) Air Velocity [m/s (ft./s)] Air Velocity [m/s (ft./s)] m ft. 5 16.4 0.3(1) m ft. 5 16.4 4 13.1 4 13.1 3 9.8 0.5(1.
Single Zone Mega, Standard Efficiency, and Mega 115V Wall Mounted Engineering Manual AIR FLOW AND TEMPERATURE DISTRIBUTION LSN240HEV2, LSN240HFV3 continued. Heating Air Velocity [m/s (ft./s)] 0.3(1) 0.5(1.6) Temperature [℃ (℉)] 1(3.3) 1.5(4.9) 2(6.6) m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.6 0 m 2 ft. 6.6 1 3.3 0 0 m 24(75) ft. 6.6 32(90) 2 30(86) 28(82) 26(79) m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.6 0 1 3.
AIR FLOW AND TEMPERATURE DISTRIBUTION LSN090HXV2 Cooling Air Velocity [m/s (ft./s)] Temperature [℃ (℉)] 2(6.6) 0.3(1) 1(3.3) 0.5(1.6) m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.6 0 m 2 ft. 6.6 1 3.3 0 0 m 26(79) 28(82) ft. 6.6 22(72) 2 24(75) m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.6 0 1 3.3 0 0 Side View Discharge Angle : 35˚ (From the floor Vertical Louver : Center Fan Speed : Power ) 0.3(1) 0.5(1.6) 1(3.3) 2(6.6) 10 32.8 8 26.2 6 19.7 4 13.1 2 6.
Single Zone Mega, Standard Efficiency, and Mega 115V Wall Mounted Engineering Manual AIR FLOW AND TEMPERATURE DISTRIBUTION LSN090HXV2, continued. Heating Air Velocity [m/s (ft./s)] Temperature [℃ (℉)] 2(6.6) 0.3(1) 0.5(1.6) 1(3.3) m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.6 0 m 2 ft. 6.6 1 3.3 0 0 28(82) 24(75) 26(79) m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.6 0 m 2 ft. 6.6 1 3.
AIR FLOW AND TEMPERATURE DISTRIBUTION LSN120HXV2 Cooling Air Velocity [m/s (ft./s)] Temperature [℃ (℉)] 2(6.6) 0.3(1) 1(3.3) 0.5(1.6) m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.6 0 m 2 ft. 6.6 1 3.3 0 0 22(72) 24(75) 26(79) 28(82) m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.6 0 m 2 ft. 6.6 1 3.3 0 0 Side View Discharge Angle : 35˚ (From the floor Vertical Louver : Center Fan Speed : Power ) 0.3(1) 0.5(1.6) 1(3.3) 2(6.6) 10 32.8 8 26.2 6 19.7 4 13.1 2 6.
Single Zone Mega, Standard Efficiency, and Mega 115V Wall Mounted Engineering Manual AIR FLOW AND TEMPERATURE DISTRIBUTION LSN120HXV2, continued. Heating Air Velocity [m/s (ft./s)] Temperature [℃ (℉)] 2(6.6) 0.3(1) 0.5(1.6) 1(3.3) m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.6 0 m 2 ft. 6.6 1 3.3 0 0 28(82) 24(75) 26(79) m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.6 0 m 2 ft. 6.6 1 3.
ACCESSORIES LG Monitoring View (LGMV) Diagnostic Software and Cable Additional screens can be accessed by tabs on the main screen: 1.
Single Zone Mega, Standard Efficiency, and Mega 115V Wall Mounted Engineering Manual ACCESSORIES LG Smart Inverter Monitoring System (SIMS) SIMS can be used to display and graph operational data for single zone systems and respective components (indoor unit and outdoor unit). SIMS also displays error codes and a troubleshooting guide. SIMs consists of a hardware Wireless Local Area Network (WLAN) module, an interface cable, and a free downloadable application (app) for iOS® or Android™.
PERFORMANCE DATA Cooling Capacity Data on page 52 Heating Capacity Data on page 62 Maximum Heating Capacity Data on page 67 Equipment Selection Procedure on page 72
PERFORMANCE DATA Single Zone Mega, Standard Efficiency, and Mega 115V Wall Mounted Engineering Manual Cooling Capacity Cooling Capacity Table for LS090HEV2 (LSU090HEV2 + LSN090HEV2) Table 16: LSN090HEV2 / LSU090HEV2 Cooling Capacities. Outdoor Air Temp. (°F DB) Indoor Air Temperature (°F DB / °F WB) 64 / 53 68 / 57 PI 72 / 61 TC SHC PI 77 / 64 TC TC SHC 86 / 72 90 / 75 TC SHC TC SHC PI PI TC SHC PI TC SHC PI 14 5.51 4.90 0.31 6.89 5.21 0.36 8.27 5.53 0.42 9.99 5.93 0.49 11.
PERFORMANCE DATA Cooling Capacity Cooling Capacity Table for LS120HEV2 (LSU120HEV2 + LSN120HEV2) Table 17: LSN120HEV2 / LSU120HEV2 Cooling Capacities. Outdoor Air Temp. (°F DB) Indoor Air Temperature (°F DB / °F WB) 64 / 53 68 / 57 72 / 61 TC SHC PI 77 / 64 TC PI TC SHC 86 / 72 PI TC SHC 90 / 75 TC SHC PI PI TC SHC PI 14 7.35 5.65 0.49 9.19 6.02 0.58 11.03 6.39 0.67 13.33 6.84 0.78 14.71 7.12 0.84 12.27 7.76 0.69 10.65 8.19 0.58 23 7.89 6.07 0.48 9.49 6.46 0.58 11.09 6.
PERFORMANCE DATA Single Zone Mega, Standard Efficiency, and Mega 115V Wall Mounted Engineering Manual Cooling Capacity Cooling Capacity Table for LS180HEV2 (LSU180HEV2 + LSN180HEV2) Table 18: LSN180HEV2 / LSU180HEV2 Cooling Capacities. Outdoor Air 64 / 53 Temp. (°F DB) TC SHC PI Indoor Air Temperature (°F DB / °F WB) 68 / 57 TC SHC 72 / 61 PI TC SHC 77 / 64 PI SHC PI TC SHC 86 / 72 PI TC SHC 90 / 75 PI TC SHC PI 14 11.02 8.76 0.64 13.78 9.32 0.76 16.54 9.89 0.87 19.99 10.60 1.02 22.
PERFORMANCE DATA Cooling Capacity Cooling Capacity Table for LS240HEV2 (LSU240HEV2 + LSN240HEV2) Table 19: LSN240HEV2 / LSU240HEV2 Cooling Capacities. Outdoor Air Temp. (°F DB) Indoor Air Temperature (°F DB / °F WB) 64 / 53 68 / 57 PI TC SHC 72 / 61 PI TC SHC PI 77 / 64 TC SHC PI 80 / 67 TC SHC 86 / 72 PI TC SHC 90 / 75 TC SHC PI TC SHC PI 14 13.47 9.98 23 14.46 10.71 0.84 17.40 11.41 1.02 20.33 12.10 1.19 24.00 12.97 1.41 26.20 13.48 1.55 23.06 14.71 1.23 20.96 15.53 1.
PERFORMANCE DATA Single Zone Mega, Standard Efficiency, and Mega 115V Wall Mounted Engineering Manual Cooling Capacity Cooling Capacity Table for LS090HFV3 (LSU090HFV3 + LSN090HFV3) Table 20: LSN090HFV3 / LSU090HFV3 Cooling Capacities. Outdoor Air 64 / 53 Temp. (°F DB) TC SHC PI Indoor Air Temperature : °F DB / °F WB 68 / 57 72 / 61 77 / 64 80 / 67 86 / 72 90 / 75 TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14 5.51 4.90 0.35 6.89 5.21 0.41 8.27 5.53 0.48 9.99 5.93 0.
PERFORMANCE DATA Cooling Capacity Cooling Capacity Table for LS120HFV3 (LSU120HFV3 + LSN120HFV3) Table 21: LSN120HFV3 + LSU120HFV3 Cooling Capacities. Indoor Air Temperature : °F DB / °F WB Outdoor Air Temp. (°F DB) TC SHC 14 7.35 5.65 0.53 9.19 6.02 0.63 11.03 6.39 0.73 13.33 6.84 0.85 14.71 7.12 0.92 12.27 7.76 0.75 10.65 8.19 0.64 23 7.89 6.07 0.53 9.49 6.46 0.64 11.09 6.86 0.75 13.09 7.35 0.88 14.29 7.64 0.97 12.58 8.34 0.77 11.43 8.80 0.64 25 8.01 6.17 0.54 9.58 6.55 0.65 11.14 6.
PERFORMANCE DATA Single Zone Mega, Standard Efficiency, and Mega 115V Wall Mounted Engineering Manual Cooling Capacity Cooling Capacity Table for LS180HFV3 (LSU180HFV3 + LSN180HFV3) Table 22: LSN180HFV3 + LSU180HFV3 Cooling Capacities. Outdoor Air 64 / 53 Temp. (°F DB) TC SHC PI Indoor Air Temperature : °F DB / °F WB 68 / 57 TC SHC 72 / 61 PI TC 9.32 0.83 16.54 SHC 9.89 77 / 64 PI SHC PI TC SHC 86 / 72 PI TC SHC 90 / 75 PI TC SHC PI 14 11.02 8.76 0.70 13.78 0.96 19.99 10.60 1.
PERFORMANCE DATA Cooling Capacity Cooling Capacity Table for LS240HFV3 (LSU240HFV3 + LSN240HFV3) Table 23: LSN240HFV3 + LSU240HFV3 Cooling Capacities. Indoor Air Temperature : °F DB / °F WB Outdoor Air Temp. (°F DB) TC 14 13.47 23 14.46 10.71 0.93 17.40 11.41 1.12 20.33 12.10 1.31 24.00 12.97 1.55 26.20 13.48 1.70 23.06 14.71 1.36 20.96 15.53 1.13 25 14.69 10.88 0.95 17.56 11.55 1.14 20.43 12.23 1.33 24.02 13.07 1.56 26.18 13.57 1.71 23.31 14.87 1.38 21.40 15.73 1.16 30 15.25 11.30 1.02 17.
PERFORMANCE DATA Single Zone Mega, Standard Efficiency, and Mega 115V Wall Mounted Engineering Manual Cooling Capacity Cooling Capacity Table for LS090HXV2 (LSU090HXV2 + LSN090HXV2) Table 24: LSN090HXV2 / LSU090HXV2 Cooling Capacities. Outdoor Air 64 / 53 Temp. (°F DB) TC SHC PI Indoor Air Temperature (°F DB / °F WB) 68 / 57 TC SHC 72 / 61 77 / 64 PI TC SHC PI TC SHC PI TC SHC 86 / 72 90 / 75 PI TC SHC PI TC SHC PI 4 5.51 4.90 0.31 6.89 5.21 0.37 8.27 5.53 0.43 9.99 5.93 0.
PERFORMANCE DATA Cooling Capacity Cooling Capacity Table for LS120HXV2 (LSU120HXV2 + LSN120HXV2) Table 25: LSN120HXV2 / LSU120HXV2 Cooling Capacities. Outdoor Air 64 / 53 Temp. (°F DB) TC SHC PI Indoor Air Temperature (°F DB / °F WB) 68 / 57 TC SHC 72 / 61 PI TC 77 / 64 SHC PI TC SHC PI 80 / 67 TC SHC 86 / 72 PI TC SHC PI 90 / 75 TC SHC PI 7.35 5.65 0.49 9.19 6.02 0.58 11.03 6.39 0.67 13.33 6.84 0.78 14.71 7.12 0.84 12.27 7.76 0.69 10.65 8.19 0.58 23 7.89 6.07 0.48 9.49 6.
PERFORMANCE DATA Single Zone Mega, Standard Efficiency, and Mega 115V Wall Mounted Engineering Manual Heating Capacity Heating Capacity Table for LS090HEV2 (LSU090HEV2 + LSN090HEV2) Table 26: LSN090HEV2 / LSU090HEV2 Heating Capacities. Outdoor Air Temp. °F DB °F WB Indoor Air Temperature (°F DB) 60 64 68 70 72 75 86 TC PI TC PI TC PI TC PI TC PI TC PI TC PI 16 14 6.90 0.70 6.69 0.69 6.62 0.69 6.55 0.68 6.50 0.68 6.37 0.68 6.22 0.68 17 15 6.94 0.71 6.73 0.70 6.
PERFORMANCE DATA Heating Capacity Heating Capacity Table for LS180HEV2 (LSU180HEV2 + LSN180HEV2) Table 28: LSN180HEV2 / LSU180HEV2 Heating Capacities. Outdoor Air Temp. °F DB °F WB Indoor Air Temperature (°F DB) 60 64 68 70 72 75 86 PI TC PI TC PI TC PI TC PI TC PI TC PI 14 12.02 1.26 11.66 1.25 11.54 1.25 11.43 1.24 11.34 1.24 11.11 1.23 10.85 1.23 17 15 12.10 1.28 11.74 1.26 11.62 1.26 11.50 1.25 11.42 1.25 11.19 1.24 10.92 1.24 19 17 12.27 1.30 11.
PERFORMANCE DATA Single Zone Mega, Standard Efficiency, and Mega 115V Wall Mounted Engineering Manual Heating Capacity Heating Capacity Table for LS090HFV3 (LSU090HFV3 + LSN090HFV3) Table 30: LSN090HFV3 / LSU090HFV3 Heating Capacities. Indoor Air Temperature (°F DB) Outdoor Air Temperature °F DB °F WB 60 64 68 70 72 75 86 TC PI TC PI TC PI TC PI TC PI TC PI TC PI 16 14 6.90 0.76 6.69 0.75 6.62 0.75 6.55 0.74 6.50 0.74 6.37 0.74 6.22 0.74 17 15 6.94 0.77 6.
PERFORMANCE DATA Heating Capacity Heating Capacity Table for LS180HFV3 (LSU180HFV3 + LSN180HFV3) Table 32: LSN180HFV3 / LSU180HFV3 Heating Capacities. Indoor Air Temperature (°F DB) Outdoor Air Temperature °F DB °F WB 60 64 68 70 72 75 86 TC PI TC PI TC PI TC PI TC PI TC PI TC PI 14 12.02 1.39 11.66 1.38 11.54 1.38 11.43 1.36 11.34 1.36 11.11 1.35 10.85 1.35 17 15 12.10 1.40 11.74 1.39 11.62 1.39 11.50 1.38 11.42 1.38 11.19 1.36 10.92 1.36 19 17 12.
PERFORMANCE DATA Single Zone Mega, Standard Efficiency, and Mega 115V Wall Mounted Engineering Manual Heating Capacity Heating Capacity Table for LS090HXV2 (LSU090HXV2 + LSN090HXV2) Table 34: LSN090HXV2 / LSU090HXV2 Heating Capacities. Outdoor Air Indoor Air Temperature (°F DB) Temp. 60 64 68 70 72 °F DB °F WB TC PI TC PI TC PI TC PI TC PI TC 75 86 PI TC 16 14 6.90 0.70 6.69 0.69 6.62 0.69 6.55 0.68 6.50 0.68 6.37 0.68 6.22 0.68 PI 17 15 6.94 0.71 6.73 0.70 6.67 0.70 6.
PERFORMANCE DATA Maximum Heating Capacity Maximum Heating Capacity Table for LS090HEV2 (LSU090HEV2 + LSN090HEV2) Table 36: LSN090HEV2 / LSU090HEV2 Heating Capacities. Outdoor Air Temp. °F DB °F WB Indoor Air Temperature (°F DB) 60 64 68 70 72 75 86 PI TC PI TC PI TC PI TC PI TC PI TC PI 14 8.37 1.15 8.25 1.17 8.13 1.18 8.08 1.19 7.84 1.17 7.51 1.15 6.22 1.06 17 15 8.68 1.16 8.56 1.18 8.44 1.19 8.39 1.20 8.14 1.18 7.80 1.14 6.44 1.01 19 17 9.17 1.16 9.
PERFORMANCE DATA Single Zone Mega, Standard Efficiency, and Mega 115V Wall Mounted Engineering Manual Maximum Heating Capacity Maximum Heating Capacity Table for LS180HEV2 (LSU180HEV2 + LSN180HEV2) Table 38: LSN180HEV2 / LSU180HEV2 Heating Capacities. Outdoor Air Temp. °F DB °F WB 60 64 TC PI TC Indoor Air Temperature (°F DB) 68 70 72 75 86 PI TC PI TC PI TC PI TC PI TC PI 16 14 14.59 2.08 14.38 2.11 14.17 2.14 14.08 2.15 13.66 2.12 13.09 2.08 10.84 1.92 17 15 15.
PERFORMANCE DATA Maximum Heating Capacity Maximum Heating Capacity Table for LS090HFV3 (LSU090HFV3 + LSN090HFV3) Table 40: LSN090HFV3 / LSU090HFV3 Heating Capacities. Indoor Air Temperature (°F DB) Outdoor Air Temperature 60 64 68 70 72 °F DB °F WB TC 75 86 TC PI TC PI TC PI TC PI TC PI TC PI 14 8.37 1.26 8.25 1.28 8.13 1.30 8.08 1.31 7.84 1.29 7.51 1.26 6.22 1.17 17 15 8.68 1.27 8.56 1.29 8.44 1.31 8.39 1.32 8.14 1.29 7.80 1.25 6.44 1.11 19 17 9.17 1.28 9.
PERFORMANCE DATA Single Zone Mega, Standard Efficiency, and Mega 115V Wall Mounted Engineering Manual Maximum Heating Capacity Maximum Heating Capacity Table for LS180HFV3 (LSU180HFV3 + LSN180HFV3) Table 42: LSN180HFV3 / LSU180HFV3 Heating Capacities. Indoor Air Temperature (°F DB) Outdoor Air Temperature 60 °F DB °F WB TC 64 PI TC 68 PI TC 70 PI TC 72 PI TC 75 PI TC 86 PI TC PI 16 14 14.59 2.28 14.38 2.32 14.17 2.35 14.08 2.36 13.66 2.33 13.09 2.28 10.84 2.11 17 15 15.14 2.31 14.
PERFORMANCE DATA Maximum Heating Capacity Maximum Heating Capacity Table for LS090HXV2 (LSU090HXV2 + LSN090HXV2) Table 44: LSN090HXV2 / LSU090HXV2 Heating Capacities. Outdoor Air Temp. °F DB °F WB Indoor Air Temperature (°F DB) 60 64 68 70 72 75 86 PI TC PI TC PI TC PI TC PI TC PI TC PI 14 8.37 1.15 8.25 1.17 8.13 1.18 8.08 1.19 7.84 1.17 7.51 1.15 6.22 1.06 17 15 8.68 1.16 8.56 1.18 8.44 1.19 8.39 1.20 8.14 1.18 7.80 1.14 6.44 1.01 19 17 9.17 1.16 9.
EQUIPMENT SELECTION PROCEDURE Single Zone Mega, Standard Efficiency, and Mega 115V Wall Mounted Engineering Manual Correction Factors Cooling / Heating Correction Factors For Single Zone Mega, Standard Efficiency, and Mega 115V Wall Mounted systems, calculate the equivalent length of the liquid line from the outdoor unit to the indoor unit. Also, determine the elevation difference of the indoor unit above or below the outdoor unit.
EQUIPMENT SELECTION PROCEDURE Correction Factors Defrost Correction Factor for Heating Operation The outdoor unit heating capacity may need to be adjusted for frost accumulation on air-cooled systems. If design day conditions are below the dewpoint of the surrounding air, frost may not be a problem and no correction factor is needed. In certain weather conditions, however, frost may form and accumulate on the air-cooled outdoor unit coil and impact the coils ability to transfer heat.
APPLICATION GUIDELINES Placement Considerations on page 75 Installing Outdoor Units Indoors on page 80 Refrigerant Piping Design on page 83
PLACEMENT CONSIDERATIONS Indoor Unit Selecting the Best Location for the Indoor Unit Follow recommended best practices when choosing an indoor location for the single zone indoor unit. Figure 30: Indoor Unit Clearance Requirements. Unit: Inch (mm) Dos >8 (200) >4 (100) >4 (100) At least 6-1/2 feet from the floor Table 50: Indoor Unit Ceiling Clearance.
PLACEMENT CONSIDERATIONS Single Zone Mega, Standard Efficiency, and Mega 115V Wall Mounted Engineering Manual Outdoor Unit Selecting the Best Location for the Outdoor Unit • DANGER Do not install the unit in an area where combustible gas will generate, flow, stagnate, or leak. These conditions can cause a fire, resulting in bodily injury or death. • Do not install the unit in a location where acidic solution and spray (sulfur) are often used as it can cause bodily injury or death.
PLACEMENT CONSIDERATIONS Outdoor Unit Planning for Snow and Ice, continued. When deciding on a location to place the outdoor unit, be sure to choose an area where run-off from defrost will not accumulate and freeze on sidewalks or driveways, which will create unsafe conditions. Properly install and insulate any drain hoses to prevent the hose from freezing, cracking, leaking, and causing unsafe conditions from frozen condensate.
PLACEMENT CONSIDERATIONS Single Zone Mega, Standard Efficiency, and Mega 115V Wall Mounted Engineering Manual Outdoor Unit Oceanside Applications Use of a Windbreak to Shield from Sea Wind Figure 34: Oceanside Placement Using Windbreak. Windbreak Ocean winds will cause corrosion, particularly on the condenser and evaporator fins, which, in turn could cause product malfunction or inefficient performance. • • • • • • Avoid installing the outdoor unit where it would be directly exposed to ocean winds.
PLACEMENT CONSIDERATIONS Outdoor Unit Minimum Allowable Clearance and Service Access Requirements Proper clearance for the outdoor unit coil is critical for proper operation. When installing the outdoor unit, consider service, inlet and outlet, and minimum allowable space requirements as illustrated in the diagrams below. • Include enough space for airflow and for service access.
PLACEMENT CONSIDERATIONS Single Zone Mega, Standard Efficiency, and Mega 115V Wall Mounted Engineering Manual Installing Outdoor Units Indoors Installing Outdoor Units Indoors Single Zone Mega, Standard Efficiency, and Mega 115V Wall Mount outdoor units are engineered to be mounted outdoors and include technology designed to minimize the negative effects of winter weather’s freezing rain, sleet, and snow.
PLACEMENT CONSIDERATIONS Installing Outdoor Units Indoors Provide a means to drain the condensate generated during heating mode and defrost cycle in addition to rainwater that infiltrates the inlet louver enclosed area. • Install a field-provided drain pan under the outdoor units and provide a path to a nearby floor drain.
PLACEMENT CONSIDERATIONS Open Rate by Louver Radian Figure 39: Open Rate by Louver Radian Formula. W h ho H ≤ 15 ho = h * COS Total Area (A) = H * W Number of Open Spaces (N) = (Number of Louvers - 1) Effective Area (Af) = ho * W * N Louver Open Rate (n) = Af / A Af = A * n Side View Effective Cross Section Area Front View Confirming Air Flow Rate / Total Opening Rate Figure 40: Example of Installing Outdoor Unit Indoors. • Example: LSU180HSV5. Louver Dimensions • Discharge Airflow Rate: 2,119 ft.
REFRIGERANT PIPING DESIGN Design Guideline Summary Device Connection Limitations Figure 41: System Layout. Single-zone systems consist of one outdoor unit and one indoor unit. One of the most critical elements of a single zone system is the refrigerant piping. The table below lists pipe length limits that must be followed in the design of a Single Zone Mega, Standard Efficiency, or Mega 115V refrigerant pipe system. Refer to the figure at right for maximum length and elevation of piping.
REFRIGERANT PIPING DESIGN Single Zone Mega, Standard Efficiency, and Mega 115V Wall Mounted Engineering Manual Design Guideline Summary Table 56: Single Zone Mega, Standard Efficiency, and Mega 115V Piping System Additional Refrigerant Charge. Model Numbers Mega, Standard Efficiency Models LS090HEV2 (LSN090HEV2 / LSU090HEV2) LS120HEV2 (LSN120HEV2 / LSU120HEV2) LS180HEV2 (LSN180HEV2 / LSU180HEV2) LS240HEV2 (LSN240HEV2 / LSU240HEV2) LS090HFV3 (LSN090HFV3 / LSU090HFV3) Additional Refrigerant Charge (oz.