58 | PERFORMANCE DATA
Single Zone Mega and Mega 115V Wall Mounted Engineering Manual
LS090HXV2, LS120HXV2
Maximum Heating Capacity
PERFORMANCE DATA
Maximum Heating Capacity Table for LS090HXV2 (LSU090HXV2 +
LSN090HXV2)
Table 31: LSN090HXV2 / LSU090HXV2 Heating Capacities.
Maximum Heating Capacity Table for LS120HXV2 (LSU120HXV2 +
LSN120HXV2)
Table 32: LSN120HXV2 / LSU120HXV2 Heating Capacities.
Outdoor Air
Temp.
Indoor Air Temperature (°F DB)
°F DB °F WB
60 64 68 70 72 75 86
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
16 14 8.37 1.15 8.25 1.17 8.13 1.18 8.08 1.19 7.84 1.17 7.51 1.15 6.22 1.06
17 15 8.68 1.16 8.56 1.18 8.44 1.19 8.39 1.20 8.14 1.18 7.80 1.14 6.44 1.01
19 17 9.17 1.16 9.05 1.18 8.92 1.19 8.76 1.20 8.58 1.17 8.19 1.13 6.68 0.99
24 23 10.07 1.17 9.93 1.18 9.80 1.18 9.74 1.18 9.36 1.15 8.83 1.11 6.89 0.95
32 30 10.97 1.13 10.84 1.14 10.70 1.14 10.64 1.14 10.13 1.10 9.43 1.05 6.95 0.86
41 38 11.84 1.05 11.70 1.07 11.55 1.10 11.49 1.11 10.90 1.05 10.09 0.99 7.33 0.73
43 40 12.20 1.01 12.05 1.03 11.91 1.05 11.84 1.06 11.22 1.01 10.37 0.93 7.47 0.67
47 43 12.93 0.97 12.78 1.00 12.63 1.04 12.52 1.05 11.90 0.99 10.99 0.91 7.90 0.63
53 50 12.74 0.94 12.58 0.97 12.42 1.01 12.45 1.02 11.61 0.96 10.61 0.86 7.29 0.53
59 53 12.59 0.92 12.58 0.96 12.57 1.00 12.46 1.02 11.77 0.95 10.68 0.86 7.19 0.54
64 57 12.81 0.90 12.62 0.91 12.42 0.93 12.33 0.94 11.57 0.88 10.53 0.80 7.11 0.52
70 61 12.86 0.85 12.63 0.85 12.40 0.85 12.30 0.85 11.55 0.80 10.52 0.73 7.14 0.47
75 65 13.05 0.77 12.78 0.79 12.51 0.82 12.28 0.83 11.62 0.78 10.58 0.70 7.08 0.43
DB: Dry Bulb Temperature (°F) WB: Wet Bulb Temperature (°F) TC: Total Capacity (kBtu/h)
PI: Power Input (kW) (includes compressor
, indoor fan motor and outdoor fan motor)
1. All capacities are net, evaporator fan motor heat is deducted.
2. Direct interpolation is permissible.
Do not extrapolate.
Capacity as rated: 0 ft. above sea level with 24.6 ft. of refrigerant piping. 0 ft. level difference between
outdoor and indoor units.
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF wet
bulb (WB), and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
Outdoor Air
Temp.
Indoor Air Temperature (°F DB)
°F DB °F WB
60 64 68 70 72 75 86
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
16 14 9.21 1.31 9.08 1.33 8.95 1.35 8.89 1.36 8.63 1.34 8.27 1.31 6.85 1.21
17 15 9.56 1.33 9.43 1.35 9.29 1.36 9.23 1.37 8.96 1.34 8.59 1.30 7.09 1.15
19 17 10.10 1.33 9.96 1.35 9.82 1.36 9.64 1.37 9.45 1.34 9.02 1.29 7.35 1.14
24 23 11.08 1.34 10.94 1.34 10.79 1.35 10.73 1.35 10.30 1.31 9.72 1.27 7.58 1.09
32 30 12.08 1.30 11.93 1.30 11.78 1.30 11.71 1.30 11.15 1.26 10.38 1.20 7.65 0.99
41 38 13.03 1.20 12.88 1.23 12.72 1.25 12.65 1.26 12.00 1.21 11.11 1.13 8.07 0.84
43 40 13.43 1.15 13.27 1.17 13.11 1.20 13.04 1.21 12.35 1.15 11.41 1.07 8.22 0.77
47 43 14.23 1.11 14.07 1.14 13.91 1.18 13.78 1.20 13.10 1.14 12.10 1.05 8.70 0.72
53 50 14.03 1.08 13.85 1.11 13.67 1.15 13.71 1.17 12.79 1.09 11.69 0.99 8.02 0.61
59 53 13.86 1.05 13.85 1.10 13.84 1.14 13.71 1.16 12.96 1.09 11.76 0.99 7.91 0.61
64 57 14.11 1.03 13.89 1.04 13.67 1.06 13.58 1.07 12.74 1.01 11.60 0.92 7.83 0.59
70 61 14.16 0.98 13.91 0.97 13.65 0.97 13.54 0.97 12.71 0.91 11.58 0.83 7.87 0.54
75 65 14.36 0.88 14.07 0.91 13.77 0.94 13.52 0.95 12.79 0.89 11.64 0.80 7.80 0.49