Installation Instructions

14
Single Zone High Efciency Wall Mounted Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
GENERAL INSTALLATION GUIDELINES
Required Clearances
Figure 4: Outdoor Unit Clearances
Outdoor Unit Clearance
12
28
24
12
24
Unit : inch
Do not place the unit where animals and/or plants will be in the path of the warm air, or where the warm air and/or noise will disturb neighbors.
Figure 5: Outdoor Unit Sunroof/Awning Clearances
More than
12
More than
12
Sunroof
Fence or
obstacles
More than
28
Unit : inch
More than
24
9/12k Indoor Units: 5
18k Indoor Units: 8
More than 4
More than 4
At least 6.5 from the floor
Unit: Inch
Indoor Unit Clearance
Follow recommended best practices when choosing an indoor loca-
tion for the Single Zone indoor unit.
Keep unit away from any indoor steam or excessive heat.
No obstacles should be placed around unit.
Condensation drain (Leakage piping) should be routed away from
the unit.
Do not install near doorway.
Clearance gap between any wall or enclosure and the left or right
side of the unit must be greater than 4 inches.
From the top of the unit to the ceiling there must be greater than 5
or 8 inches of clearance (depending on indoor unit model).
Unit should be at least 6.5 feet from the oor for adequate clearance.
Figure 6: Clearances Where There Are Obstacles on Both Air
Inlet and Outlet Sides (Obstacle on the Outlet Side is Lower
Than the Outdoor Unit)
Figure 7: Clearances Where There are Obstacles Above and on Both Air Inlet
and Outlet Sides (Obstacle on the Outlet Side is Lower Than the Outdoor Unit)
Figure 8: Indoor Unit Clearance Recommendations
Minimum
28
Minimum
12
Unit: Inch
Minimum
12
79
24
Minimum 28
Unit: Inch