Installation Manual
11
ENGLISH
ELECTRICAL CONNECTIONS
4-WIRE CONNECTION WITH 
A POWER SUPPLY CORD
• 
Only a 4-conductor power-supply cord kit rated 
120/240 volts, 50 amperes and marked for use 
with ranges with closed-loop connectors or open-
end spade lugs with upturned ends shall be used. 
The middle (neutral) wire, which is white, of the 
power cord or 4-wire conduit has to be connected 
to the middle post of the main terminal block. 
The other two wires of the power cord or conduit 
have to be connected to the outside posts of the 
main terminal connection block. The 4th ground 
wire (green) must be connected to the frame of 
the range with the ground screw.
-   Failure to do so can result in electrical shock, 
severe personal injury or death.
 WARNING
Install the power cord as follows:
For power cord installations, Hook  the strain relief  over 
the power cord hole (1
3
/
8
”) located below the rear of 
oven. Insert the power cord through the strain relief and 
tighten it. (Refer to Figure 7.)
DO NOT install the power cord without a strain relief.
1. Remove the lower 3 screws from the terminal block 
and retain them. (Refer to Figure 9.)
2. Remove ground  strap  and  discard  as  show  in  in  
Figure 9.
3. 
 Insert the ground screw into the power cord ground wire 
(green) terminal ring and secure it to the range frame.
4. 
Insert the 3 screws through each power cord terminal ring 
and into the lower terminals of the terminal block. Make sure 
that the center (neutral) wire, which is white, is connected to 
the center lower position of the terminal block.
5.  Tighten 3 screws securely into the terminal block.
4-wire connection
Terminal 
block
Conduit
connection plate
Ground screw
Remove ground
strap and discard
Ground 
strap
Black White Red
FIGURE 9
3-WIRE CONNECTION: CONDUIT
Install the conduit as follows:
Remove the Conduit connection plate from the rear of 
oven and rotate it as shown in Figure 5. The conduit hole 
(1
1
/
8
") must be used.
First, prepare the conduit wires as shown in Figure 10.
  3 wire  4 wire
Conduit
connection 
plate
 or 
Ground 
wire
FIGURE 10
Second, install conduit as shown in Figure 6.
For conduit installations, after purchasing a strain relief, 
insert it in the conduit hole (1
1
/
8
”). Then install  the 
conduit through the body of strain relief and fasten the 
strain relief with its ring. Reinstall the bracket.
For conduit connections :
If the wire in the conduit is copper  it must be 8 or 10 
AWG wiring.
If the wire in the conduit is aluminum it must be 6 or 8 
AWG wiring.
1. Loosen the lower 3 screws from the terminal block. 
Refer to Figure 11.)
2. Insert the bare wire (white/neutral) end through the 
center terminal block opening. Do not remove ground 
strap connections.
3. Insert the two side bare wire ends into the lower left 
and the lower right terminal block opening. Tighten 
the  3  screws  securely  into  the  terminal  block. 
(approximately 35 - 50 IN-LB)
4. Refer to page 13.
3-wire connection
Terminal 
block
Wire ends
Conduit
connection plate
Black White Red
FIGURE 11
* If screws are not tightened securely, it can result in electrical spark and severe personal injury or death.