Installation Manual
12 Multi Air Conditioner
Installation of Indoor, Outdoor Unit
Multi Piping Type
Piping length and elevation
h2
h1
A
B
Multiple Piping Type
Unit : m(ft)
18 50(164) 25(82) 3(10) 15(49) 7.5(25) 24
24 70(230) 25(82) 3(10) 15(49) 7.5(25) 33
24(RED) 75(246) 25(82) 3(10) 15(49) 7.5(25) 33
30 75(246) 25(82) 3(10) 15(49) 7.5(25) 40
36 75(246) 25(82) 3(10) 15(49) 7.5(25) 48
Outdoor Unit
Capacity
(kBtu/h class)
Max total length
of all pipes
(A+B)/(A+B+C)/
(A+B+C+D)
Max length of
each pipe
(A/B/C/D)
Min length of
each pipe
(A/B/C/D)
Max Elevation
between each
indoor unit and
outdoor unit (h1)
Max elevation
between indoor
units (h2)
Max.Combination
of Indoor unit
(kBtu/h class)
Indoor unit Capacity (kBtu/h class)
Pipe Diameter
Unit : mm(inch)
Gas Liquid
7, 9, 12, 15 9.52(3/8) 6.35(1/4)
15(Console), 18, 24 12.7(1/2) 6.35(1/4)
36 15.88(5/8) 9.52(3/8)
To calculate the connected total indoor unit nominal capacity, simply sum up the nominal capacities of all indoor
units.
• For high static duct and vertical-horizontal air handling indoor units, a 1.3 multiplier must first be applied before
adding to the sum of other indoor units (when connected to an outdoor unit other than the LMU600HV).
• When high static duct and / or vertical-horizontal air handling indoor units are the only connected indoor units,
the multiplier is 1.2.
CAUTION
Capacity is based on standard length and maximum allowance length is on the
basis of reliability.
!