FINAL INSTALLATION PROCEDURES
Forced Cooling Operation Function
Use to add refrigerant to the system when outside ambient temperatures are cool (ex.: winter).
1. Shut power down to the system.
2. Set DIP Switch 1 to ON.
3. Turn power on to the system.
4. Verify that the Red LED on the outdoor unit
PCB is ON (indicates indoor units are in forced
cooling operation).
5. Add refrigerant.
If the green LED light on the outdoor unit PCB is ON, it indicates the compressor is OFF due to low
pressure in the system.
Turn DIP Switch 1 to OFF after finishing (Normal Operation setting).
Only the first four DIP switches are used to set settings and functions.
Location of DIP Switches on Multi F and Multi F MAX Outdoor Units
Figure 114: Multi F (LMU180-240HV) Outdoor Unit DIP Switch Locations. Figure 115: Multi F (LMU30-36CHV) Outdoor Unit DIP Switch Locations.
DIP SW1 DIP SW1
LMU180 / 240HV (18 / 24 kBtu/h)
LMU180HV
(18 kBtu/h)
12 43
12 43
ON
OFF
5
5
LMU240HV
(24 kBtu/h)
12 43
12 43
ON
OFF
5
5
SW1
LMU30CHV / LMU36CHV (30 / 36 kBtu/h)
12 43
12 43
ON
OFF
5
5
DIP_SW01D
LMU601HV (60 kBtu/h)
12 43
12 43
ON
OFF
5
5
6
6
Figure 116: Multi F MAX (LMU481-541HV) Outdoor Unit DIP Switch
Locations.
Figure 117: Multi F MAX (LMU601HV) Outdoor Unit DIP Switch Locations.
Figure 118: LMU180-240HV-30-
36CHV Forced Cooling DIP Switch
Setting.
DIP_SW01D
6
LMU481HV / LMU541HV (48 / 54 kBtu/h)
12 43
ON
OFF
5
Figure 119: LMU481-541-601HV
Forced Cooling DIP Switch Setting.
1234
56
ON
OFF