5. Trouble Shooting
1.3 Error Indicator (Outdoor)
Outdoor Error
Ex) Error 21 (DC Peack)
1 Time 1 Time 1 Time
2 Times2 Times2 Times
1 Sec.
2 Sec. 2 Sec.
1 Sec. 1 Sec.
LED01G
(RED)
LED02G
(GREEN)
Error
Contents
LED01G/M LED02G/M
Case of Error
Outdoor
Code (Red) (Green) Status
21 DC Peak (IPM Fault) 2times
◑
1time
◑
Over Rated Current Off
22 CT 2(Max CT) 2times
◑
2times
◑
Input Over Current Off
23 DC Link Low Volt. 2times
◑
3times
◑
DC Link Volt is below 140Vdc Off
24 L_P/H_P Switch 2times
◑
4times
◑
Low/High Press Switch Open Off
25 Low Voltage/Over Voltage 2times
◑
5times
◑
Abnormal AC Volt Input Off
26 DC Compressor Position Error 2times
◑
6times
◑
Compressor Starting Fall Error Off
27 PSC/PFC Fault Error 2times
◑
7times
◑
Inverter PCB input current is over100A(peak) for 2us
Off
28 DC Link High Volt 2times
◑
8times
◑
Off Off
29 COMP Over Current 2times
◑
9times
◑
Over Inverter Compressor Current Off
32 D-Pipe High (INV) 3times
◑
2times
◑
Off Off
40 CT Sensor (Open / Short) 4times
◑ O
CT Circuit Malfunction Off
41 INV. D-Pipe Th Error 4times
◑
1time
◑
Open/Short Off
44 Outdoor Air Th Error 4times
◑
4times
◑
Open/Short Off
45 Cond. Pipe Th Error 4times
◑
5times
◑
Open/Short Off
46 Suction Pipe Error 4times
◑
6times
◑
Open/Short Off
51 Capacity Over 5times
◑
1time
◑
Over combination Off
52 Signal Error(DSP Board <-> Main Board) 5times
◑
2times
◑
Communication Poorly Off
53 Signal Error (Indoor <-> Outdoor) 5times
◑
3times
◑
Communication Poorly Off
60 EEPROM Check Sum Error 6times
◑ O
Check Sum Mismatching Off
61 Cond. Pipe Th High 6times
◑
1time
◑
Cond. Temp. High Off
62 Heatsink Th High 6times
◑
2times
◑
Heatsink Temp. High Off
65 Heatsink Th Error 6times
◑
5times
◑
Open/Short Off
67 Outdoor BLDC Fan Lock 6times
◑
7times
◑
Outdoor Fan is not operating Off
73 PFC Fault Error(S/W) 7times
◑
3times
◑
Over Current of Outdoor Unit PFC Off