EQUIPMENT SELECTION PROCEDURE
Cooling/Heating Correction Factors
For Single Zone Art Cool Mirror systems, calculate the equivalent length of the liquid line from the outdoor unit to the indoor unit. Also, de-
termine the elevation difference of the indoor unit above or below the outdoor unit. Find corresponding cooling or heating capacity correction
factors as shown in Figures 5 through 8. Multiply the correction factors by the cooling or heating capacity obtained from the capacity tables
using design conditions. The resultant is the NET cooling or heating capacity.
Figure 5: LA090HSV4,LA120HSV4CoolingCoefcientFactor.
Figure 6: LA090HSV4,LA120HSV4HeatingCoefcientFactor.