Engineering Manual

Due to our policy of continuous product innovation, some specications may change without notication.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
PRODUCT DATA | 49
Product Data
PERFORMANCE DATA
Maximum Heating Capacity
Table 22: LA180HSV5 Maximum Heating Capacities.
Maximum Heating Capacity Table for LA180HSV5 (LAU180HSV5 +
LAN180HSV5)
Outdoor Air
Temp.
Indoor Air Temperature (°F DB / °F WB)
60 64 68 70 72 75 86
°FDB °FWB TC PI TC PI TC PI TC PI TC PI TC PI TC PI
-3 -4 16.99 2.30 16.89 2.30 16.81 2.31 16.76 2.31 16.65 2.34 16.39 2.38 15.61 2.54
0 -1 17.95 2.32 17.81 2.34 17.70 2.35 17.63 2.36 17.50 2.39 17.21 2.44 16.33 2.60
1 0 18.35 2.33 18.19 2.35 18.07 2.38 18.00 2.39 17.86 2.41 17.53 2.44 16.56 2.55
6 5 20.37 2.40 20.16 2.43 19.99 2.46 19.30 2.48 19.70 2.46 19.25 2.43 17.18 2.34
10 9 21.44 2.43 21.20 2.46 21.00 2.49 20.90 2.51 20.63 2.49 20.03 2.45 17.49 2.33
16 14 22.43 2.45 22.17 2.48 21.95 2.52 21.83 2.53 21.47 2.50 20.66 2.45 18.21 2.27
17 15 22.68 2.44 22.41 2.48 22.20 2.52 22.08 2.54 21.69 2.50 20.82 2.44 18.22 2.23
19 17 22.96 2.47 22.68 2.49 22.46 2.52 22.34 2.53 21.91 2.48 20.95 2.40 18.07 2.12
24 23 25.99 2.72 25.69 2.73 25.44 2.73 25.30 2.74 24.68 2.67 23.30 2.58 19.14 2.24
32 30 30.84 3.08 30.48 3.09 30.19 3.10 30.03 3.10 29.12 3.01 27.07 2.88 20.92 2.38
41 38 36.30 3.36 35.88 3.42 35.54 3.48 35.35 3.51 34.17 3.37 31.51 3.17 23.52 2.40
43 40 37.52 3.45 37.08 3.52 36.73 3.58 36.53 3.62 35.26 3.46 32.39 3.23 23.79 2.38
47 43 39.96 3.68 39.49 3.80 39.11 3.92 38.90 3.98 37.46 3.79 34.24 3.50 24.56 2.46
53 50 41.00 3.75 40.49 3.86 40.07 3.97 39.84 4.03 38.27 3.81 34.74 3.48 24.13 2.28
59 53 41.52 3.67 41.48 3.81 41.45 3.95 41.43 4.02 39.73 3.80 35.89 3.48 24.37 2.29
64 57 41.85 3.59 41.23 3.65 40.72 3.70 40.44 3.73 38.81 3.54 35.14 3.26 24.12 2.24
70 61 41.99 3.43 41.26 3.43 40.67 3.42 40.33 3.42 38.72 3.25 35.10 2.99 24.21 2.06
75 65 41.89 3.13 41.04 3.22 40.35 3.30 39.96 3.35 38.32 3.17 34.62 2.90 23.53 1.92
Table 23: LA240HSV3 Maximum Heating Capacities.
Outdoor Air
Temp.
Indoor Air Temperature (°F DB/ °F WB)
°F DB °F WB
60 64 68 70 72 75 86
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
-3 -4 21.31 3.48 21.20 3.49 21.08 3.49 21.03 3.50 20.84 3.54 20.57 3.61 19.58 3.84
0 -1 22.52 3.52 22.36 3.54 22.19 3.56 22.12 3.58 21.90 3.62 21.60 3.69 20.49 3.94
1 0 23.01 3.55 22.84 3.58 22.66 3.61 22.58 3.62 22.34 3.65 22.00 3.69 20.79 3.84
6 5 24.79 3.65 24.56 3.70 24.32 3.75 24.22 3.77 23.89 3.74 23.44 3.70 21.78 3.56
10 9 26.21 3.67 25.94 3.72 25.67 3.77 25.55 3.80 25.11 3.76 24.51 3.71 22.30 3.53
16 14 27.86 3.70 27.56 3.75 27.26 3.80 27.13 3.82 26.51 3.77 25.68 3.69 22.63 3.43
17 15 28.11 3.73 27.80 3.78 27.49 3.83 27.35 3.86 26.73 3.78 25.88 3.67 22.75 3.27
19 17 28.79 3.74 28.48 3.78 28.16 3.82 28.02 3.84 27.29 3.76 26.30 3.64 22.67 3.22
24 23 30.50 3.77 30.17 3.78 29.84 3.79 29.69 3.80 28.71 3.70 27.37 3.57 22.46 3.10
32 30 32.25 3.65 31.90 3.66 31.55 3.67 31.39 3.67 30.10 3.56 28.34 3.40 21.87 2.82
41 38 33.89 3.41 33.53 3.47 33.16 3.54 33.00 3.56 31.50 3.41 29.46 3.20 21.96 2.43
43 40 34.24 3.26 33.87 3.32 33.50 3.39 33.34 3.42 31.76 3.26 29.61 3.04 21.71 2.25
47 43 34.72 3.14 34.34 3.25 33.97 3.35 33.80 3.40 32.10 3.22 29.80 2.98 21.34 2.10
53 50 35.62 3.20 35.21 3.30 34.80 3.40 34.62 3.44 32.76 3.24 30.24 2.96 20.97 1.95
59 53 36.07 3.14 36.04 3.26 36.01 3.38 36.00 3.43 33.99 3.23 31.24 2.96 21.17 1.96
64 57 36.36 3.07 35.86 3.11 35.36 3.16 35.14 3.19 33.21 3.01 30.58 2.78 20.96 1.91
70 61 36.48 2.93 35.90 2.93 35.31 2.92 35.05 2.92 33.14 2.76 30.55 2.55 21.04 1.76
75 65 36.39 2.68 35.71 2.75 35.03 2.83 34.72 2.86 32.78 2.69 30.14 2.47 20.44 1.64
Maximum Heating Capacity Table for LA240HSV3 (LAU240HSV3 +
LAN240HSV3)
DB: Dry Bulb Temperature (°F) WB: Wet Bulb Temperature (°F) TC: Total Capacity
(kBtu/h)
PI: Power Input (kW) (includes compressor, indoor fan motor, and outdoor fan motor)
1. All capacities are net, evaporator fan motor heat is deducted.
2. Direct interpolation is permissible. Do not extrapolate.
Nominal capacity as rated: 0 ft. above sea level with 25 ft. of refrigerant piping.
0 ft. level difference between outdoor and indoor units.
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb
(DB) and 60ºF wet bulb (WB), and outdoor ambient conditions of 47ºF dry bulb (DB) and
43ºF wet bulb (WB).
LA180HSV5, LA240HSV3