Engineering Manual

Due to our policy of continuous product innovation, some specications may change without notication.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
22 | PRODUCT DATA
Single Zone Art Cool
TM
Mirror Wall Mount Engineering Manual
Model
Sound Pressure Levels (dB[A])
Cooling (Max) Heating (Max.)
LSU090HSV5 45 48
LSU120HSV5 45 48
LSU180HSV5 53 53
LAU240HSV3 53 53
Table 7: Art Cool Mirror Outdoor Unit Acoustic Data
Figure 17: Outdoor Unit Sound Level Measurement.
3.28 ft
Center of
Outdoor Unit
Outdoor Unit Sound Pressure Level Measurement
Outdoor Unit Sound Pressure Levels
ACOUSTIC DATA
Outdoor Units
Measurements are taken 3.3 ft away from the front of the unit.
Sound pressure levels are measured in dB(A) with a tolerance of
±3.
Data is valid at nominal operation conditions. Operating conditions
are assumed to be standard.
Reference acoustic pressure 0dB=20μPa
Sound pressure levels are tested in an anechoic chamber under
ISO Standard 3745, and may be different according to the test
condition or equipment.
Sound level will vary depending on a range of factors including the
construction (acoustic absorption coefficient) of a particular room in
which the unit was installed.
Figure 18: LSU090/120HSV5 Cooling Sound Pressure Level Diagram.
Figure 19: LSU090/120HSV5 Heating Sound Pressure Level Diagram.