Datasheet
Website Information 5RMI0-02A
150
Inverter Single
Outdoor unit
H09AK UL2
Indoor unit
/ H09AK NSM
Function (indicate if present)
If function includes heating: Indicate the heating
season the information relates to. Indicated values
should relate to one heating season at a time. Include
at least the heating season 'Average'.
cooling Y Average (mandatory) Y
heating Y Warmer (if designated) N
Colder (if designated) N
Item symbol value unit Item symbol value unit
Design load Seasonal efficiency
cooling Pdesignc 2.5 kW cooling SEER 9.1 -
heating / Average Pdesignh 3.2 kW heating / Average SCOP/A 5.2 -
heating / Warmer Pdesignh x,x kW heating / Warmer SCOP/W x,x -
heating / Colder Pdesignh x,x kW heating / Colder SCOP/C x,x -
Declared capacity* for cooling, at indoor temperature
27(19)ºC and outdoor temperature Tj
Declared Energy efficiency ratio* for cooling, at indoor
temperature 27(19)ºC and outdoor temperature Tj
Tj=35ºC Pdc 2.5 kW Tj=35ºC EERd 5.2 -
Tj=30ºC Pdc 1.8 kW Tj=30ºC EERd 7.1 -
Tj=25ºC Pdc 1.2 kW Tj=25ºC EERd 11.2 -
Tj=20ºC Pdc 1.0 kW Tj=20ºC EERd 14.9 -
Declared capacity* for heating / Average climate, at indoor
temperature 20ºC and outdoor temperature Tj
Declared Coefficient of performance* for heating /
Average climate, at indoor temperature 20ºC and outdoor
temperature Tj
Tj=-7ºC Pdh 3.1 kW Tj=-7ºC COPd 3.4 -
Tj=2ºC Pdh 1.7 kW Tj=2ºC COPd 5.0 -
Tj=7ºC Pdh 1.2 kW Tj=7ºC COPd 6.5 -
Tj=12ºC Pdh 0.9 kW Tj=12ºC COPd 7.8 -
Tj=bivalent temperature Pdh 3.4 kW Tj=bivalent temperature COPd 3.0 -
Tj=operating limit Pdh 3.3 kW Tj=operating limit COPd 3.3 -
Declared capacity* for heating / Warmer climate, at indoor
temperature 20ºC and outdoor temperature Tj
Declared Coefficient of performance* / Warmer climate,
at indoor temperature 20ºC and outdoor temperature Tj
Tj=2ºC Pdh x,x kW Tj=2ºC COPd x,x -
Tj=7ºC Pdh x,x kW Tj=7ºC COPd x,x -
Tj=12ºC Pdh x,x kW Tj=12ºC COPd x,x -
Tj=bivalent temperature Pdh x,x kW Tj=bivalent temperature COPd x,x -
Tj=operating limit Pdh x,x kW Tj=operating limit COPd x,x -
Declared capacity* for heating / Colder climate, at indoor
temperature 20ºC and outdoor temperature Tj
Declared Coefficient of performance* / Colder climate, at
indoor temperature 20ºC and outdoor temperature Tj
Tj=-7ºC Pdh x,x kW Tj=-7ºC COPd x,x -
Tj=2ºC Pdh x,x kW Tj=2ºC COPd x,x -
Tj=7ºC Pdh x,x kW Tj=7ºC COPd x,x -
Tj=12ºC Pdh x,x kW Tj=12ºC COPd x,x -
Tj=bivalent temperature Pdh x,x kW Tj=bivalent temperature COPd x,x -
Tj=operating limit Pdh x,x kW Tj=operating limit COPd x,x -
Tj=-15ºC Pdh x,x kW Tj=-15ºC COPd x,x -
Bivalent temperature Operating limit temperature
heating / Average Tbiv -8 ºC heating / Average Tol -10 ºC
heating / Warmer Tbiv x ºC heating / Warmer Tol x ºC
heating / Colder Tbiv x ºC heating / Colder Tol x ºC
Cycling interval capacity Cycling interval efficiency
for cooling Pcycc x,x kW for cooling EERcyc x,x -
for heating Pcych x,x kW for heating COPcyc
x,x
-
Degradation co-efficient
cooling**
Cdc 0.25 -
Degradation co-efficient
heating**
Cdh 0.25 -
Electric power input in power modes other than 'active
mode'
Annual electricity consumption
off mode P
OFF
0.018 kW cooling Q
CE
96
kWh/a
standby mode P
SB
0.018 kW heating / Average Q
HE
862
kWh/a
thermostat-off mode P
TO
0.013 kW heating / Warmer Q
HE
x
kWh/a
crankcase heater mode P
CK
0 kW heating / Colder Q
HE
x
kWh/a
Capacity control (indicate one of three options) Other items
fixed N
Sound power level
(indoor/outdoor)
L
WA
57 /
65
dB(A)
staged N Global warming potential GWP 1975
kg CO2 eq.
variable Y Rated air flow (indoor/outdoor) -
990/
1980
m3/h
Contact details for obtaining
more information
Christianna PAPAZAHARIOU
Internal communicator - Energy & environment regulations expert
,LGElectronics
Paris Nord II – 117 avenue des Nations
BP 59372 Villepinte – 95942 Roissy CDG Cedex
chris.papazahariou@lge.com
Tel. +33 1 49 89 57 41 , +33 6 83 077 455
*= For staged capacity units, two values divided by a slash (‘/’) will be declared in each box in the section “Declared
capacity of the unit” and "declared EER/COP" of the unit.
**= If default Cd=0,25 is chosen then (results from) cycling tests are not required. Otherwise either the heating or cooling
cycling test value is required.
Model : AS-W096MMS3(H09AK)