Datasheet

Installation5RMI0-02A
147
Inverter Single
Selecting the location(Outdoor Unit)
1) If the outdoor unit is to be installed close to the seaside, then direct exposure to the sea wind should be avoided.
Install the outdoor unit on the opposite side of the sea wind direction.
- It should be strong enough like concrete to prevent the
sea wind from the sea.
- The height and width should be more than 150% of the
outdoor unit.
- Keep more than 70 cm of space between outdoor unit
and the windbreak for easy air flow.
2) In case of installing the outdoor unit on the sea side, setup a windbreak to prevent sea wind.
3) Select a well-drained place.
CAUTION
1. Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced.
2. Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion on the
product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient
performance.
3. If outdoor unit is installed close to the seaside, it should avoid direct exposure to the sea wind. Otherwise it needs
additional anticorrosion treatment on the heat exchanger.
Sea wind
Sea wind
Sea wind
Windbreak
1. If you cant meet above guide line in the seaside installation, please contact LG Electronics for the additional
anticorrosion treatment.
2. Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger by using
water
* Do not use seawater when you clean up the heat exchanger.
Installation Guide for Areas Exposed to Sea Wind