Inverter Single
Indoor
Connect the cable to the indoor unit by connecting the
wires to the terminals on the control board individually
according to the outdoor unit connection. (Ensure that the
color of the wires of the outdoor unit and the terminal No.
are the same as those of the indoor unit.)
1. Insert the connecting cable through the bottom side of
indoor unit and connect the cable.
2. Secure the cable onto the control board with the cable
retainer.
3. Lift up the cover of terminal block slightly.
4. Tape the tubing pipe, drain hose and the connection
cable. Be sure that the drain hose is located at the
lowest side of the bundle. Locating at the upper side
can cause overflow from the drain pan through the
inside of the unit.
•
The circuit diagram is a subject to change without notice.
•
The earth wire should be longer than the common wires.
• When installing, refer to the circuit diagram on the
chassis cover.
• Connect the wires firmly so that they may not be pulled
out easily.
• Connect the wires according to color codes, referring to
the wiring diagram.
The power cord connected to unit should be
selected according to the following national wiring
regulations.
The supply cords of parts of appliances for outdoor
use shall not be lighter than polychloroprene
sheathed flexible cord.
(code designation 60245 IEC 57, H05RN-F)
CAUTION
CAUTION
The power connecting cable with indoor and
outdoor unit should be selected according to the
following national wiring regulations.
The supply cords of parts of appliances for outdoor
use shall not be lighter than polychloroprene
sheathed flexible cord.
(code designation 60245 IEC 57, H05RN-F)
- Connect the wires to the terminals on the control board
individually.
- Secure the cable onto the control board with the cord
clamp.
- Use a recognized circuit breaker between the power
source and the unit.
A disconnecting device to adequately disconnect all
supply lines must be fitted.
Control Cover
10±3mm
20mm
GN/YL
10±3mm
20mm
GN/YL
Connecting the Cables
NOMINAL
CROSS -
SECTIONAL
AREA
Grade
2.5~3.5kW
1.0
(mm
2
)
NOMINAL
CROSS -
SECTIONAL
AREA
Grade
2.5~3.5kW
1.0
(mm
2
)
Circuit
Breaker(A)
Grade
2.5~3.5kW
15